GENERATOR BUILDS VOLTAGE FROM STARTUP, THEN GOES TO LOW (RESIDUAL) VOLTAGE

CAUSE

CHECK AND REMEDY

Regulator protective circuit operating

Check indicators on regulator. Correct problems and adjust regulator as is required. Refer

 

to regulator manual.

GENERATOR IS OVERHEATING

CAUSE

Generator is overloaded Clogged ventilating screens High room temperature or altitude Insufficient circulation of cooling air

Unbalanced load

CHECK AND REMEDY

Reduce load. Check with ammeter and compare with nameplate rating.

Clean air passages.

Improve ventilation or reduce load.

Generator location and enclosure design must provide adequate airflow and minimize recirculation of hot air.

The load on each leg should be as evenly balanced as possible and should not exceed rated current on any one leg.

GENERATOR PRODUCES MECHANICAL NOISE

CAUSE

CHECK AND REMEDY

Defective bearing

Replace bearing.

Loose or misaligned coupling

Tighten, realign, or replace coupling.

Belt slap or loose guards

Check belt tensioning. Check belt guard fasteners.

EQUIPMENT RUNS NORMALLY ON UTILITY POWER, BUT WILL NOT RUN ON GENERATOR

CAUSE

CHECK AND REMEDY

Distorted voltage waveform

Analyze load. Excessive SCR (thyristor) loading will cause distortion. Some equipment

 

may be sensitive to distorted waveforms. Refer to Marathon Electric.

Improper generator voltage or

Check nameplates of devices comprising the load. Compare required voltage and

frequency

frequency with that of the generator. Adjust driver speed and/or generator voltage as

 

necessary to match generator output to load requirements.

CAUTION: Compare required voltage, frequency, and kVA with generator nameplate to ensure adequate generator capacity. If in doubt, consult Marathon Electric for information regarding generator capacity.

19

Page 44
Image 44
Baldor TS45, BALDOR GENERATORS, TS25, TS80, TS175, TS130 manual Generator is Overheating, Generator Produces Mechanical Noise