OVERHEATING (continued)

CAUSE

CHECK AND REMEDY

High room temperature.

Improve ventilation.

Insufficient circulation.

Provide cross–ventilation.

Low power factory.

Reduce inductive loads or install power factor im-

 

provement capacitors.

Unbalanced load

The load on each leg should be as evenly balanced

 

as possible and should not exceed the rated cur-

 

rent on any leg.

Dry bearing.

Replace bearing.

 

MECHANICAL NOISE

CAUSE

CHECK AND REMEDY

Defective bearing.

Replace bearing.

Rotor scrubbing on stator.

Bad bearing; replace. Bent shaft, return to factory.

 

Loosen end bell, tighten; loose drive discs, tighten.

Loose laminations.

Return to factory.

Loose or misaligned coupling.

Tighten or align.

GENERATOR FRAME PRODUCES SHOCK WHEN TOUCHED

CAUSE

CHECK AND REMEDY

Static charge.

Ground generator frame.

Grounded armature or field coil.

Return to factory for repair.