6 en NoticeRemote Command Center

1

Notice

 

 

These instructions cover the installation of the Bosch FMR-1000-RCMD Remote Command

 

 

Center in a fire system supervised by a Bosch FPA-1000 Analog Addressable Fire Panel or a

 

 

Fire Alarm Control Panel with similar connection conditions.

 

 

Install, test and maintain the FMR-1000-RCMD according to these instructions, NFPA 72,

 

 

Local Codes, and the Authority Having Jurisdiction. Failure to follow these instructions may

 

 

result in failure of the device to operate properly. Bosch Security Systems Inc. is not

 

 

responsible for improperly installed, tested or maintained devices.

 

 

Refer to FPA-1000- Installation and Operation Guide (P/N F.01U.174.607) for detailed wiring

 

 

style requirements and complete programming instructions.

 

 

 

 

NOTICE!

 

NFPA 72 requires a complete system-wide functional test be performed following any

 

modifications, repair, upgrades, or adjustments made to the system’s components, hardware,

 

wiring, programming, and software/firmware.

 

 

 

 

 

 

 

CAUTION!

 

These instructions contain procedures to follow in order to avoid personal injury and damage

 

to equipment.

 

 

 

2

Scope of Delivery

 

 

 

 

 

Description

 

 

 

 

 

One Remote Command Center (in back box with cover frame)

 

 

 

 

 

Tabs with different language versions for LED and key text

 

 

 

 

 

One hardware pack

 

 

 

 

 

One FMR-1000-RCMD Installation and Operation Guide

 

 

 

3

Device Description

 

 

The Remote Command Center FMR-1000-RCMD is a four-wire LCD annunciator with system

 

 

control capability. It shows the LEDs and LCD display identically to the panel’s and includes a

piezo, scrolling buttons, and operation keys for acknowledge [ACK], drill, reset and silence. The scrolling functions and the acknowledge [ACK] key are accessible without restriction. The keys for reset, silence or drill can be enabled and disabled by the device key lock. In addition, the operation keys or all keys can be locked using DIP switches (refer to Table 7.1 on

Page 11).

The Remote Command Center features tabs with different language versions for LED and key text. The device allows for surface and semi-flush mounting.

Each FPA-1000 Analog Addressable Fire Panel supports up to a total of eight FMR-1000-RA Remote Annunciators and/or FMR-1000-RCMD Remote Command Centers.