Remote Command CenterOperating en 13
LED |
| System Status | |
|
|
|
|
Trouble | On | – | When the panel is initializing |
Yellow |
| – | When the panel registers a trouble condition from a point, or the panel |
–When inputs or outputs or other elements are bypassed
Flashing 1) – When the panel is not operating
–When walk test is in progress
Off | – When no trouble condition exists |
–When the panel is resetting
1)LED flash rate is 1 Hz (0.5 s on, 0.5 s off).
Table 9.1 LED Operation
Display
The
Piezo Sounder
The
Piezo Operation | System Status |
|
|
Silent | The panel is in a normal state (no alarm, supervisory or trouble |
| condition). The panel was silenced or acknowledged after an off- |
| normal condition. |
|
|
Continuous beep | The panel is in fire alarm condition. |
|
|
Periodic beep | The panel is in gas alarm condition. |
(0.5 s every 2 s) |
|
|
|
Periodic beep | The panel is in supervisory condition. |
(0.5 s every 4 s) |
|
|
|
Periodic beep | The panel is in trouble condition or a communication fault exists |
(0.5 s every 10 s) | on the Option Bus. |
|
|
Short beep | With every valid key press. |
|
|
Table 9.2 Piezo Operation with
In case of multiple piezo activation, the system status with highest priority is indicated. If the Remote Command Center is not controlled by the panel or during a communication fault, refer to Table 9.3 for piezo modes:
Piezo Operation | System Status with |
|
|
Periodic beep | A communication fault exists on the Option Bus. |
(0.5 s every 10 s) |
|
|
|
Table 9.3 Piezo Operation with
Bosch Security Systems, Inc. | Installation and Operation Guide | F.01U.078.098 3.0 2011.11 |