On a D1260 Keypad:

GV2 Series Control Panels Owner's Manual Supplement

4.Press the [ENT] key to activate the selected walk test function. The keypad shows the number of testable points within the scope of the keypad: ### PTS TO TEST

5.Press the [NEXT] key to see VIEW UNTESTED?

6.Press the [ENT] key to view the untested points. The keypad shows the total number of untested points within the keypad scope: ### PTS UNTESTED.

7.Press the [NEXT] key to view the first point’s name.

8.Press the [ENT] key to view the point’s hardware state. Refer to Table 2.

Table 2: Hardware States of Points

Display Text

Hardware State

 

 

1PT### NORMAL HW

Normal

1PT### OPEN HW

Opened

 

 

1PT### SHORT HW

Shorted

1PT### MISSNG HW

Missing

9.Activate the point’s sensor and observe the appropriate state change.

10.Press the [NEXT] key to advance to the next untested point within the scope of the keypad.

11.Repeat steps 8 through 10 until all points are tested.

On a D1260 Keypad:

1.If you use the command sequence, press the keys indicated in the Command Sequence column of Table 1 on page 10 for the necessary walk test. The keypad shows the number of testable points within the scope of the keypad: ### points remain to be tested. Proceed to Step 5.

2.If you use the menu function list, press the [Menu>] soft key in the lower right corner.

3.Press the [Next >] soft key until the Menu Function Name (refer to Table 1 on page 10) appears.

4.Press the corresponding soft key to activate the necessary Walk Test functions.

The keypad shows the number of testable points within the scope of the keypad: ### points remain to be tested.

Bosch Security Systems, Inc. 2/07 F01U063791-01