Figure 18. Vent Terminal (Low Ground Clearance)

Maximum Vent Length Determination

Power Vent Maximum Vent Length

Model

Max Vent Length (feet)

Max Vent Length (feet)

Number

3" PVC, CPVC, or ABS

4" PVC, CPVC, or ABS

EF60T125, EF100T150

120

170

EF60T150, EF100T199

100

150

EF60T199, EF100T250

80

130

EF100T300

60

120

Table 4

Determining required vent length:

1.Determine the total length of straight vent pipe (in feet) required.

2.Add 5 feet of venting for every 90° elbow.

3.Add 2 ½ feet of venting for every 45° elbow.

4.Total vent length can not exceed “Max. Vent Length” in Table 4.

NOTICE

Do not include the 3” exhaust elbow or vent terminals in determining maximum vent length.

COAXIAL VENTING INSTALLATION PROCEDURE

WARNING

Improper installation, adjustment, service, or maintenance can cause property damage, personal injury, or death. Consult a qualified installer, service agency, or the gas supplier for information or assistance.

This kit must be used only for terminating this water heater. Do not use this termination kit for any other appliance. Using this kit on other appliances and/or water heaters can result in property damage, personal injury, or death.

DO NOT operate this water heater until the installation and assembly of this kit is complete and the piping completed. Failure to complete installation before operation can result in property damage, personal injury, or death.

Before beginning any installation, be sure the main electrical disconnect switch is in the OFF position. Electrical