BSPP Generator

RECEPTACLES

The generator will be equipped with one or more of the following receptacles:

CAUTION

Receptacles may be marked with rating value greater than generator output capacity.

NEVER attempt to power a device requiring more amperage than generator or receptacle can supply.

DO NOT overload the generator. See “Don’t Overload Generator”.

120/240 Volt AC, 30 Amp, Locking Receptacle

Use a NEMA L14–30 plug with this receptacle. Connect a 4–wire cord set rated for 250 Volts AC at 30 Amps (or greater) (Figure 5).You can use the same 4–wire cord if you plan to run a 120 Volt load.

Figure 5 — 120/240 Volt AC, 30 Amp Receptacle

4-Wire Cord Set

240V

120V 120V

W (Neutral)

Y (Hot)

X (Hot)

NEMA L14-30

Ground (Green)

This receptacle powers 120/240 Volt AC, 60 Hz, single phase loads requiring up to 3,600 watts of power at

30 Amps for 120 Volts; 7,200 watts of power (7.2 kW) at 30 Amps for 240 Volts.The outlet is protected against overload by a push–to–reset circuit breaker and/or a 2 pole GFCI circuit breaker.

120/240 Volt AC, 20 Amp Locking Receptacle

Use a NEMA L14-20 plug with this receptacle. Connect a 4-wire cord set rated for 250 Volts AC at 20 Amps (or greater) (Figure 6).You can use the same 4-wire cord if you plan to run a 120 Volt load.

Figure 6 — 120/240 Volt AC, 20 Amp Receptacle

4-Wire Cord Set

240V

120V 120V

W (Neutral)

Y (Hot)

X (Hot)

NEMA L14-20

Ground (Green)

This receptacle powers 120/240 Volt AC, 60 Hz, single phase loads requiring up to 2,400 watts of power at

20 Amps for 120 Volts; 4,800 watts of power (4.8 kW) at 20 Amps for 240 Volts.The outlet is protected against overload by a push–to–reset circuit breaker and/or a 2 pole GFCI circuit breaker.

9

Page 9
Image 9
Briggs & Stratton PRO4000 01932, PRO6500 01933 owner manual Receptacles, 120/240 Volt AC, 30 Amp, Locking Receptacle