Status Codes

Table 6 shows the status codes flashed by the amber status light. Most system problems can be diagnosed by reading the status code as flashed by the amber status light on the control board.

The codes are flashed by a series of short and long flashes of the status light. The short flashes indicate the first digit in the status code, followed by long flashes indicating the second digit of the error code. The short flash is 0.25 seconds ON and the long flash is 1.0 second ON. Time between flashes is 0.25 seconds. Time

between short flash and first long flash is 1.0 second. Time between code repeating is 2.5 seconds with LED OFF.

Count the number of short and long flashes to determine the appropriate flash code. Table 6 gives possible causes and actions related to each error.

EXAMPLE:

3 short flashes followed by 2 long flashes indicates a 32 code. Table 6 shows this to be low pressure switch open.

Table 6 – TROUBLESHOOTING

 

 

AMBER

 

OPERATION

FAULT

LED

POSSIBLE CAUSE AND ACTION

FLASH

 

 

 

 

 

CODE

 

Standby – no call for unit operation

None

On solid, no

Normal operation

flash

 

 

 

low---stage Cool/Heat Operation

None

1, pause

Normal operation

high ---stage Cool/Heat Operation

None

2, pause

Normal operation

 

System Commu-

16

Communication with user interface lost. Check wiring to User Interface,

 

nications Failure

 

indoor and outdoor units

 

 

 

 

 

Invalid Model Plug

25

Control does not detect a model plug or detects an invalid model plug. Unit

 

will not operate without correct model plug.

 

 

 

 

High Pressure

31*

High ---pressure switch trip. Check refrigerant charge, outdoor fan operation

 

Switch Open

and coils for airflow restrictions.

 

 

 

Low Pressure

32*

Low pressure switch trip. Check refrigerant charge and indoor air flow

 

Switch Open

 

 

 

 

Control Fault

45

Outdoor unit control board has failed. Control board needs to be replaced.

 

Brown Out (230 v)

46

Line voltage < 187v for at least 4 seconds. Compressor and fan operation

 

not allowed until voltage>190v. Verify line voltage.

 

 

 

 

 

 

There is no 230v at the contactor when indoor unit is powered and cooling/

 

No 230v at Unit

47

heating demand exists. Verify the disconnect is closed and 230v wiring is

 

 

 

connected to the unit.

 

Outdoor Air Temp

53

Outdoor air sensor not reading or out of range. Ohm out sensor and check

 

Sensor Fault

wiring.

 

 

 

Outdoor Coil Sen-

55

Coil sensor not reading or out of range. Ohm out sensor and check wiring.

 

sor Fault

 

 

 

 

Thermistors out of

56

Improper relationship between coil sensor and outdoor air sensor. Ohm out

 

range

sensors and check wiring.

 

 

 

low---stage Ther-

 

Compressor operation detected then disappears while low---stage demand

 

71*

exists. Possible causes are internal compressor overload trip or start relay

 

mal Cutout

 

 

and capacitor held in circuit too long(if installed)

 

 

 

 

high ---stage Ther-

 

Compressor operation detected then disappears while high ---stage demand

 

72*

exists. Possible causes are internal compressor overload trip or start relay

 

mal Cutout

 

 

and capacitor held in circuit too long (if installed)

 

 

 

 

Contactor Shorted

73

Compressor voltage sensed when no demand for compressor operation

 

exists. Contactor may be stuck closed or there is a wiring error.

 

 

 

 

No 230V at Com-

 

Compressor voltage not sensed when compressor should be starting. Con-

 

pressor

74

 

tactor may be stuck open or there is a wiring error.

 

(180A Only)

 

 

 

 

 

low---stage Did Not

 

Specified start voltage at VR terminal was not achieved in low---stage. Start

 

Start

75

 

relay was de---energized after 1 second.

 

(187A Only)

 

 

 

 

 

low---stage Did Not

 

For 3 consecutive low---stage starts, the specified start voltage at VR terminal

 

Start 3 times

76

was not achieved & start relay was de---energized. low---stage locked out for

 

(187AOnly)

 

30 minutes.

 

high ---stage Did

 

Specified start voltage at VS terminal was not achieved in high ---stage. Start

 

Not Start

77

 

relay was de---energized after 1 second.

 

(187A Only)

 

 

 

 

 

high ---stage Did

 

For 3 consecutive high ---stage starts, the specified start voltage at VS termi-

 

Not Start 3 times

78

nal was not achieved & start relay was de---energized. high ---stage locked

 

(187A Only)

 

out for 30 minutes.

 

low---stage Ther-

81

Thermal cutout occurs in three consecutive low/ high ---stage cycles. low---

 

mal Lockout

stage locked out for 4 hours or until 24v power recycled.

 

 

 

high ---stage Ther-

82

Thermal cutout occurs in three consecutive high/low---stage cycles. high ---

 

mal Lockout

stage locked out for 4 hours or until 24v power recycled.

 

 

 

Low Pressure

83

Low pressure switch trip has occurred during 3 consecutive cycles. Unit

 

Lockout

operation locked out for 4 hours or until 24v power recycled.

 

 

 

High Pressure

84

High pressure switch trip has occurred during 3 consecutive cycles. Unit

 

Lockout

operation locked out for 4 hours or until 24v power recycled.

 

 

 

Low Contactor

 

Compressor voltage not sensed when compressor should be starting. low---

 

Open

85

 

stage contactor may be stuck open or there is a wiring error.

 

(187A Only)

 

 

 

 

 

High Contactor

 

Compressor voltage not sensed when compressor should be starting. high ---

 

Open

87

 

stage contactor may be stuck open or there is a wiring error.

 

(187A Only)

 

 

 

 

*Sequence: Compressor contactor is de---energized and outdoor fan is energized for up to 15 minutes. If demand still exists, control will energize compressor contactor after 15 minute delay. If fault is cleared, unit will resume operation. If fault still exists, fan shuts off, and error code continues to flash. Control will attempt re---start every 15 minutes. Cycling low voltage defeats the 15 minute delay.

180A / 187A

13

Page 13
Image 13
Bryant 180A installation instructions Status Codes, Example, Troubleshooting