should extend below level of furnace gas controls. Place a ground joint union between furnace gas control valve and exterior manual equipment gas shutoff valve.

A 1/8-in. (3 mm) NPT plugged tapping, accessible for test gauge connection, MUST be installed immediately upstream of gas supply connection to furnace and downstream of manual equipment shutoff valve.

Piping should be pressure and leak tested in accordance with the current addition of the NFGC in the United States, local, and national plumbing and gas codes before the furnace has been connected. After all connections have been made, purge lines and check for leakage at furnace prior to operating furnace.

 

If pressure exceeds 0.5 psig (14-In. W.C.), gas supply pipe must

 

be disconnected from furnace and capped before and during

 

supply pipe pressure test. If test pressure is equal to or less than

 

0.5 psig (14-In. W.C.), turn off electric shutoff switch located on

 

furnace gas control valve and accessible manual equipment

315AAV

shutoff valve before and during supply pipe pressure test. After

all connections have been made, purge lines and check for

 

 

leakage at furnace prior to operating furnace.

 

The gas supply pressure shall be within the maximum and

 

minimum inlet supply pressures marked on the rating plate with

 

the furnace burners ON and OFF.

2” (51mm)

Street Elbow

A08551

Fig. 21 - Burner and Manifold

GAS

SUPPLY

MANUAL

SHUTOFF

VALVE (REQUIRED)

SEDIMENT TRAP

UNION

A02035

Fig. 22 - Typical Gas Pipe Arrangement

ELECTRICAL CONNECTIONS

!WARNING

ELECTRICAL SHOCK HAZARD

Failure to follow this warning could result in personal injury or death.

Blower access panel door switch opens 115-v power to control. No component operation can occur. Do not bypass or close switch with panel removed.

See Fig. 25 for field wiring diagram showing typical field 115-v wiring. Check all factory and field electrical connections for tightness.

Field-supplied wiring shall conform with the limitations of 63_F (33_C) rise.

!WARNING

ELECTRICAL SHOCK AND FIRE HAZARD

Failure to follow this warning could result in personal injury, death, or property damage.

The cabinet MUST have an uninterrupted or unbroken ground according to NEC ANSI/NFPA 70-2008 or local codes to minimize personal injury if an electrical fault should occur. This may consist of electrical wire, conduit approved for electrical ground or a listed, grounded power cord (where permitted by local code) when installed in accordance with existing electrical codes. Refer to the power cord manufacturer’s ratings for proper wire gauge. Do not use gas piping as an electrical ground.

!CAUTION

FURNACE MAY NOT OPERATE HAZARD

Failure to follow this caution may result in intermittent furnace operation.

Furnace control must be grounded for proper operation or else control will lock out. Control must remain grounded through green/yellow wire routed to gas valve and manifold bracket screw.

115-V Wiring

Verify that the voltage, frequency, and phase correspond to that specified on unit rating plate. Also, check to be sure that service provided by utility is sufficient to handle load imposed by this equipment. Refer to rating plate or Table 7 for equipment electrical specifications.

U.S. Installations: Make all electrical connections in accordance with National Electrical Code (NEC) ANSI/NFPA 70-2008 and any local codes or ordinances that might apply.

20

Page 20
Image 20
Bryant 315AAV instruction manual Electrical Connections Electrical Shock Hazard, Electrical Shock and Fire Hazard, Wiring