Table 7 – Electrical Data
FURNACE | VOLTS | OPERATING | MAX. UNIT | UNIT | MAX. WIRE | MAX. FUSE OR | MIN. | |||||
HERTZ | VOLTAGE RANGE | AMPACITY | WIRE | |||||||||
| SIZE | AMPS | LENGTH | CKT BKR AMPS { | ||||||||
| PHASE |
|
| # | GAUGE | |||||||
| Max. | Min. | ||||||||||
12/036070 | 1 | 127 | 104 | 9.0 | 11.99 | 30 (9.0) | 15 | 14 | ||||
16/048090 | 1 | 127 | 104 | 9.6 | 12.56 | 29 (8.8) | 15 | 14 | ||||
20/060110 | 1 | 127 | 104 | 15.1 | 19.33 | 29 (8.8) | 20 | 12 | ||||
22/066135 | 1 | 127 | 104 | 14.9 | 19.13 | 30 (9.0) | 20 | 12 | ||||
22/066155 | 1 | 127 | 104 | 15.0 | 19.23 | 29 (8.8) | 20 | 12 |
* Permissible limits of the voltage range at which the unit operates satisfactorily.
#Unit ampacity = 125 percent of largest operating component’s full load amps plus 100 percent of all other potential operating components’ (EAC, humidifier, etc.) full load amps.
}Length shown is as measured 1 way along wire path between furnace and service panel for maximum 2 percent voltage drop.
!WARNING
FIRE HAZARD
Failure to follow this warning could result in personal injury, death, or property damage.
Do not connect aluminum wire between disconnect switch and furnace. Use only copper wire.
Use a separate, fused branch electrical circuit with a properly sized fuse or circuit breaker for this furnace. See Table 7 for wire size and fuse specifications. A readily accessible means of electrical disconnect must be located within sight of the furnace.
NOTE: Proper polarity must be maintained for
J-Box Relocation
Factory
Installed
Alternate
Location
A10291
Fig. 23 - Relocating J-Box
315AAV
NOTE: If factory location of
NOTE: On
1.Remove and save two screws holding
NOTE: The
2.Cut wire tie on loop in furnace wires attached to
3.Move
4.Fasten
5.Route
Electrical Connection to
Electrical Box on Furnace Casing Side (See Fig. 24.)
!WARNING
FIRE OR ELECTRICAL SHOCK HAZARD
Failure to follow this warning could result in personal injury, death, or property damage.
If
1.Select and remove a hole knockout in the casing where the electrical box is to be installed.
NOTE: Check that duct on side of furnace will not interfere with installed electrical box.
2.Remove the desired electrical box hole knockout and posi- tion the hole in the electrical box over the hole in the fur- nace casing.
3.Fasten the electrical box to casing by driving two field- supplied screws from inside electrical box into casing steel.
4.Remove and save two screws holding
5.Pull furnace power wires out of
6.Route furnace power wires through holes in casing and electrical box and into electrical box.
7.Pull field power wires into electrical box.
8.Remove cover from furnace
9.Route field ground wire through holes in electrical box and casing, and into furnace
10.Reattach furnace
11.Secure field ground wire to
12.Complete electrical box wiring and installation. Connect line voltage leads as shown in Fig. 24. Use best practices (NEC in U.S. for wire bushings, strain relief, etc.
13.Reinstall cover to