Bryant 315AAV instruction manual Adapter Kit, Blocked vent switch used in Chimney, A02108B

Models: 315AAV

1 60
Download 60 pages 15.94 Kb
Page 57
Image 57
Adapter Kit

CONTROLCIRCUITRYLOCKOUT

Auto-resetafter1hourlockoutdueto:

- Flamecircuitfailure.

- Gasvalverelaystuckopen.

- Softwarecheckerror.

Resetpowertoclearlockout.

45

 

 

 

 

 

LOW-HEATPRESSURESWITCHOPEN

WHILEHIGH-HEATPRESSURE

SWITCHISCLOSED- Checkfor:

- Low-heatpressureswitchstuckopen.

- Disconnectedorobstructedpressure

tube.

43

 

 

 

 

 

Replacecontrolifcoderepeats.

Replacefurnacecontrol.

Checkforcontinuityintheharnessand igniter.Replacedefectivecomponent.

 

NO

YES

- Miswiredpressureswitches. - Lowinletgaspressure(ifLGPSused).

Unplugigniterharnessfromcontroland repeatcomponenttestbyturningsetupswitch

SW1-6OFFandthenbackON.Checkfor 115Vbetweenpin3andNEUTRAL-L2on thecontrol.Was115Vpresentforthe15 secondperiod?

Checkconnections.IfOK,replacecontrol.

Checkthatallgasvalvesareturnedon. Replacevalve.

 

NO

 

NO

ReconnecttheRthermostatleadandset thermostattocallforheat.Connectvoltmeter acrossgasvalveconnections.Doesgas valvereceive24V?

YES

Doesgasvalveopenandallowgastoflow?

Checkfor: - Inadequateflamecarryoverorrough ignition.

- Lowinletgaspressure. - Properfiringrate. - Blockedorincorrectcarry-overgap. (.045”nominal)

Allowblowertocomeonandrepeattest tocheckforintermittentoperation.

NO

YES

 

YES

ignite?

YES

stayon?

NO

 

Dothemainburners

 

Dothemainburners

 

Checkconnectionsandretry.Ifcurrentis neartypicalvalue(4.0-6.0nominal)and

burnerswillnotstayon,repeatcheckinhigh- heat.Ifburnerswillstillnotstayonreplace

control.Ifburnersoperateinhigh-heatthen

switchtolow-heat,checkmanifoldpressure.

IfOK,checkburnercarryoverandflame sensorlocation.

Replaceelectrode.

 

Replacefurnacecontrol.

 

 

NO

 

 

 

 

NO

 

NO

 

 

Repeatcallforheatandcheckflamesensor currentduringtrialforignitionperiod.Isthe DCmicroampsbelow0.5?

YES

Cleanflamesensorwithfinesteelwooland

recheckcurrent.Nominalcurrentis4.0to

6.0microamps.

Iscurrentneartypicalvalue?

YES

Willmainburnersigniteandstayon?

YES

Fixed.

 

 

 

NO

 

 

 

 

YES

 

Adapter Kit

315AAV

LOW-HEATPRESSURESWITCHDID

NOTCLOSEORREOPENED–Ifopen

longerthan5minutes,inducershutsoff

for15minutesbeforeretry.Ifopens duringbloweron-delayperiod,blowerwill comeonfortheselectedbloweroff-delay. Checkfor:

32

 

 

 

NOPREVIOUSCODE–Statuscodes

areerasedafter72hoursorcanbe

manuallyerasedbyputtingsetupswitch

SW1-1intheONpositionandjumpering R,W/W1,andY/Y2simultaneouslyuntil statuscode#11isflashed.Runsystem

11

 

 

 

Properventsizing. Lowinducervoltage(115V). Lowinletgaspressure(ifLGPSused). Inadequatecombustionairsupply. Disconnectedorobstructedpressure tubing.

Defectiveinducermotor. Defectivepressureswitch. Excessivewind. Restrictedvent.

- - - - -

- - - -

throughalow-heat,high-heat,orcooling cycletochecksystem.

BLOWERONAFTERPOWERUP– (115VOR24V)–Normaloperation. Blowerrunsfor90seconds,ifunitis poweredupduringacallforheat(R- W/W1closed)orwhen(R-W/W1opens) duringthebloweron-delayperiod.

 

12

33 LIMIT CIRCUIT FAULT – Indicates the 13 LIMIT CIRCUIT LOCKOUT – Lockout

limit, draft safeguard, flame rollout, or occurs if the limit, draft safeguard, flame

blocked vent switch* (if used) is open or rollout, or blocked vent switch* (if used)

the furnace is operating in high-heat only is open longer than 3 minutes or 10

mode due to 2 successive low-heat limit successive limit trips occurred during

trips. Blower will run for 4 min. or until high-heat. Control will auto-reset after 3

open switch remakes whichever is longer. hours. See code 33.

If open longer than 3 min., code changes

to lockout #13. If open less than 3 min. status code #33 continues to flash until blower shuts off. Flame rollout switch and BVSS requires manual reset. Check for: - Dirty filter or restricted duct system. - Loose blower wheel.

14 IGNITION LOCKOUT – System failed to ignite gas and prove flame in 4 attempts. Control will auto-reset after 3 hours. See status code 34.

- Defectiveswitchorconnections. - Inadequatecombustionairsupply

(flamerolloutswitchopen).

- Restrictedvent.

- Properventsizing.

- Excessivewind.

IGNITIONPROVINGFAILURE–Ifflame isnotsensedduringthetrialforignition

period,thecontrolwillrepeattheignition

sequence3moretimesbeforelockout

#14occurs.Ifflamesignalislostduring

thebloweron-delayperiod,blowerwill comeonfortheselectedbloweroff-delay. Checkthefollowingitemsfirstbefore

proceedingtothenextstep.

- Gasvalveturnedoff.

- Manualshut-offvalve.

- Green/YellowwireMUSTbeconnected

tofurnacesheetmetal.

- Flamesensormustnotbegrounded. Todeterminewhethertheproblemisin thegasvalve,igniter,orflamesensorthe

systemcanbeoperatedincomponent

testmode.Tochecktheigniterremove

theRthermostatconnectionfromthe control,resetpower,andputsetupswitch SW1-6intheONpositiontostartthe

componenttest.Doestheigniterglow

orange/whitebytheendofthe15second

warm-upperiod?

 

 

 

 

 

34

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

BLOWERMOTORLOCKOUT–Indicates

theblowerfailedtoreach250RPMor

theblowerfailedtocommunicatewithin

30secondsafterbeingturnedONintwo

successiveheatingcycles.Controlwill auto-resetafter3hours.Seecode41.

GASHEATINGLOCKOUT–Turnoff

powerandwait5minutestoretry.

Checkfor:

- Stuckclosedgasvalverelayoncontrol.

- Miswireorshorttogasvalvewire.

ABNORMALFLAME-PROVINGSIGNAL

Flameisprovedwhilegasvalveisde-

energized.Inducerwillrununtilfaultis

cleared.Checkfor:

- Stuckopenorleakygasvalve.

PRESSURESWITCHDIDNOTOPEN

Checkfor:

- Obstructedpressuretube.

- Pressureswitchstuckclosed.

SECONDARYVOLTAGEFUSEISOPEN

Checkfor:

- Shortcircuitinsecondaryvoltage (24V)wiringincludingthermostat leads.Disconnectthermostatleads toisolateshortcircuit.

15

 

 

 

 

21

 

 

 

 

22

 

 

 

 

23

 

 

 

24

 

 

* Blocked vent switch used in Chimney

A02108B

57