III.HAZARDOUS LOCATIONS
TO BURNERS
A93044
WARNING: When furnace is installed in a residential garage, it must be installed so that burners and ignition sources are located a minimum of 18 in. above floor. The furnace must be located or protected to avoid physical damage by vehicles. When furnace is installed in a public garage, airplane hangar, or other building having a hazardous atmosphere, unit must be installed in accor- dance with requirements of National Fire Protection Association, Inc.
AIR FOR COMBUSTION AND VENTILATION
I.GENERAL
Provisions for adequate combustion and ventilation air must be provided in accordance with Section 5.3, Air for Combustion and Ventilation, of the NFGC or applicable provisions of the local building codes.
Canadian installations must be in accordance with Section 7 of the NSCNGPIC and all authorities having jurisdiction.
CAUTION: Air for combustion must not be contami- nated by halogen compounds, which include fluoride, chloride, bromide, and iodide. These elements are found in aerosol sprays, detergents, bleaches, cleaning solvents, salts, air fresheners, and other household products.
All
CAUTION: The operation of exhaust fans, kitchen ven- tilation fans, clothes dryers, fireplaces, or other appli- ances including attic and crawlspace exhaust fans could create a negative air pressure condition at the furnace.
The requirements for combustion and ventilation air depend upon whether the furnace is located in a CONFINED or UNCONFINED space.
II.UNCONFINED SPACE
An unconfined space must have at least 50 cu ft for each 1000 Btuh of total input for all the appliances (such as furnaces, clothes dryers, water heaters, etc.) in the space.
Ð13Ð
For Example:
MINIMUM FLOOR AREA FOR UNCONFINED SPACE
345MAV Furnace | Minimum Sq Ft With |
Input Btuh | |
40,000 | 267 |
60,000 | 400 |
80,000 | 533 |
100,000 | 667 |
120,000 | 800 |
|
|
If the unconfined space is of unusually tight construction, air for combustion and ventilation MUST come from either the outdoors or spaces freely communicating with the outdoors. Combustion and ventilation openings must be sized the same as for a confined space as defined below. Return air must not be taken from the room unless an equal or greater amount of air is supplied to the room.
III.CONFINED SPACE
A confined space has a volume of less than 50 cu ft per 1000 Btuh of the total input rating for all appliances installed in that space. A confined space MUST have 2 permanent openings, 1 within 12 in. of the ceiling, and the other within 12 in. of the floor which freely communicate with an unconfined space or the outdoors. (See Fig. 12 or 13.)
NOTE: In determining the free area of an opening, the blocking effect of the louvers, grilles, and screens must be considered. If the free area of a louver or grille design is unknown, it may be assumed that wood louvers have a 20 percent free area, and metal louvers or grilles have a 60 percent free area. Screens, when used, must not be smaller than
The size of the openings depends upon whether the air comes from outside of the structure or an unconfined space inside the structure.
A.All Air from Inside the Structure
1.Each opening MUST have at least 1 sq in. of free area per 1000 Btuh of the total input for all equipment within the confined space, but not less than 100 sq in. per opening. (See Fig. 12.) The minimum dimension of air openings shall not be less than 3 in.
For Example:
COMBUSTION AIR FROM UNCONFINED SPACE
345MAV Furnace | Free Area per Opening |
Input Btuh | (Sq In.) |
40,000 | 100 |
60,000 | 100 |
80,000 | 100 |
100,000 | 100 |
120,000 | 120 |
2.If the building is constructed unusually tight, in addition to the 2 permanent openings that freely communicate with an unconfined space, a permanent opening directly communi- cating with the outdoors should be provided. This opening shall have a minimum free area of 1 sq in. per 4000 Btuh of total input rating for all equipment in the enclosure.
3.If the furnace is installed on a raised platform to provide a
B.All Air from Outside the Structure
1.If combustion air is taken from outdoors through vertical ducts, the openings and ducts MUST have at least 1 sq in. of free area per 4000 Btuh of the total input for all equipment within the confined space. (See Fig. 13.)