TABLE 4ÐMAXIMUM ALLOWABLE VENT PIPE LENGTH (FT)
ALTITUDE (FT) | UNIT SIZE | VENT PIPE |
|
|
| NUMBER OF 90° ELBOWS |
|
| |||
DIAMETER (IN.) | 1 | 2 | 3 |
| 4 | 5 | 6 | ||||
|
|
| |||||||||
|
|
|
|
|
|
|
|
|
|
|
|
| 024040 | 1 | 5 |
| NA | NA | NA | NA | NA | ||
|
|
|
|
|
|
|
|
|
|
| |
| 70 | 70 | 65 |
| 60 | 60 | 55 | ||||
| 036040 |
| |||||||||
|
|
|
|
|
|
|
|
|
|
| |
| 2 | 70 | 70 | 70 |
| 70 | 70 | 70 | |||
|
|
| |||||||||
|
|
|
|
|
|
|
|
|
|
|
|
| 024060 | 20 | 15 | 10 |
| 5 | NA | NA | |||
| 036060 |
|
|
|
|
|
|
|
|
|
|
| 2 | 70 | 70 | 70 |
| 70 | 70 | 70 | |||
| 048060 |
| |||||||||
|
|
|
|
|
|
|
|
|
|
|
|
0 to 2000 | 036080 | 10 |
| NA | NA | NA | NA | NA | |||
048080 | 2 | 55 | 50 | 35 |
| 30 | 30 | 20 | |||
|
| ||||||||||
| 060080 |
|
|
|
|
|
|
|
|
|
|
| 70 | 70 | 70 |
| 70 | 70 | 70 | ||||
|
|
|
|
|
|
|
|
|
|
|
|
| 048100 | 2 | 5 |
| NA | NA | NA | NA | NA | ||
| 40 | 30 | 20 |
| 20 | 10 | NA | ||||
| 060100 |
| |||||||||
| 3 | 70 | 70 | 70 |
| 70 | 70 | 70 | |||
|
|
| |||||||||
| 060120 | 10 |
| NA | NA | NA | NA | NA | |||
| 3* | 70 | 70 | 70 |
| 70 | 70 | 70 | |||
|
|
| |||||||||
|
|
|
|
|
|
|
|
|
|
|
|
ALTITUDE (FT) | UNIT SIZE | VENT PIPE |
|
|
| NUMBER OF 90° ELBOWS |
|
| |||
DIAMETER (IN.) |
| 1 |
| 2 | 3 |
| 4 | 5 | 6 | ||
|
|
|
|
| |||||||
| 024040 |
| 67 |
| 62 | 57 |
| 52 | 52 | 47 | |
| 036040 | 2 |
| 70 |
| 70 | 70 |
| 70 | 70 | 70 |
|
|
|
|
|
|
|
|
|
|
|
|
| 024060 |
| 17 |
| 12 | 7 |
| NA | NA | NA | |
| 036060 |
|
|
|
|
|
|
|
|
|
|
| 2 |
| 70 |
| 67 | 66 |
| 61 | 61 | 61 | |
| 048060 |
|
|
| |||||||
2001 to 3000 |
|
|
|
|
|
|
|
|
|
|
|
036080 | 2 |
| 49 |
| 44 | 30 |
| 25 | 25 | 15 | |
| 048080 |
|
|
|
|
|
|
|
|
|
|
|
| 70 |
| 70 | 70 |
| 70 | 70 | 70 | ||
| 060080 |
|
|
| |||||||
|
|
|
|
|
|
|
|
|
|
|
|
| 048100 |
| 35 |
| 26 | 16 |
| 16 | 6 | NA | |
| 060100 | 3 |
| 70 |
| 70 | 70 |
| 70 | 66 | 61 |
|
|
|
|
|
|
|
|
|
|
|
|
| 060120 | 3* |
| 63 |
| 62 | 62 |
| 61 | 61 | 61 |
|
|
|
|
|
|
|
|
|
|
| |
ALTITUDE (FT) | UNIT SIZE | VENT PIPE |
|
|
| NUMBER OF 90° ELBOWS |
|
| |||
DIAMETER (IN.) |
| 1 |
| 2 | 3 |
| 4 | 5 | 6 | ||
|
|
|
|
| |||||||
| 024040 |
| 64 |
| 59 | 54 |
| 49 | 48 | 43 | |
| 036040 | 2 |
| 70 |
| 70 | 70 |
| 70 | 70 | 70 |
| 024060 |
| 16 |
| 11 | 6 |
| NA | NA | NA | |
| 036060 |
|
|
|
|
|
|
|
|
|
|
| 2 |
| 68 |
| 63 | 62 |
| 57 | 57 | 56 | |
| 048060 |
|
|
| |||||||
3001 to 4000 | 036080 | 2 |
| 46 |
| 41 | 28 |
| 23 | 22 | 13 |
| 048080 |
|
|
|
|
|
|
|
|
|
|
|
| 70 |
| 70 | 70 |
| 70 | 70 | 70 | ||
| 060080 |
|
|
| |||||||
| 048100 |
| 33 |
| 24 | 15 |
| 14 | 5 | NA | |
| 060100 | 3 |
| 70 |
| 70 | 70 |
| 66 | 61 | 56 |
|
|
|
|
|
|
|
|
|
|
|
|
| 060120 | 3* |
| 59 |
| 59 | 58 |
| 57 | 57 | 56 |
|
|
|
|
|
|
|
|
|
|
| |
ALTITUDE (FT) | UNIT SIZE | VENT PIPE |
|
|
| NUMBER OF 90° ELBOWS |
|
| |||
DIAMETER (IN.) |
| 1 |
| 2 | 3 |
| 4 | 5 | 6 | ||
|
|
|
|
| |||||||
| 024040 |
| 60 |
| 55 | 50 |
| 45 | 44 | 39 | |
| 036040 | 2 |
| 70 |
| 70 | 70 |
| 70 | 70 | 70 |
| 024060 |
| 15 |
| 10 | 5 |
| NA | NA | NA | |
| 036060 |
|
|
|
|
|
|
|
|
|
|
| 2 |
| 64 |
| 59 | 58 |
| 53 | 52 | 52 | |
| 048060 |
|
|
| |||||||
4001 to 5000² | 036080 | 2 |
| 44 |
| 39 | 26 |
| 21 | 20 | 11 |
| 048080 |
|
|
|
|
|
|
|
|
|
|
|
| 70 |
| 70 | 70 |
| 70 | 70 | 70 | ||
| 060080 |
|
|
| |||||||
| 048100 |
| 31 |
| 22 | 13 |
| 12 | NA | NA | |
| 060100 | 3 |
| 70 |
| 70 | 67 |
| 62 | 57 | 52 |
| 060120 | 3* |
| 56 |
| 55 | 54 |
| 53 | 52 | 52 |
* Wide radius elbow.
²Vent sizing for Canadian installations over 4500 ft (1370 m) above sea level are subject to acceptance by the local authorities having jurisdiction. NAÐNot Allowed; pressure switch will not make.
NOTES:
1. Do not use pipe size greater than those specified in table or incomplete combustion, flame disturbance, or flame sense lockout may occur.
2. Assume two 45° elbows equal one 90° elbow. Long radius elbows are desirable and may be required in some cases.
3. Elbows and pipe sections within the furnace casing and at the vent termination should not be included in vent length or elbow count.
4. The minimum pipe length is 5 ft for all applications.