Bryant 345MAV instruction manual Ðmaximum Allowable Vent Pipe Length Ft, Ð25Ð

Models: 345MAV

1 40
Download 40 pages 58.13 Kb
Page 25
Image 25

TABLE 4ÐMAXIMUM ALLOWABLE VENT PIPE LENGTH (FT)

ALTITUDE (FT)

UNIT SIZE

VENT PIPE

 

 

 

NUMBER OF 90° ELBOWS

 

 

DIAMETER (IN.)

1

2

3

 

4

5

6

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

024040

1

5

 

NA

NA

NA

NA

NA

 

 

 

 

 

 

 

 

 

 

 

 

1-1/2

70

70

65

 

60

60

55

 

036040

 

 

 

 

 

 

 

 

 

 

 

 

 

2

70

70

70

 

70

70

70

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

024060

1-1/2

20

15

10

 

5

NA

NA

 

036060

 

 

 

 

 

 

 

 

 

 

 

2

70

70

70

 

70

70

70

 

048060

 

 

 

 

 

 

 

 

 

 

 

 

 

0 to 2000

036080

1-1/2

10

 

NA

NA

NA

NA

NA

048080

2

55

50

35

 

30

30

20

 

 

 

060080

 

 

 

 

 

 

 

 

 

 

 

2-1/2

70

70

70

 

70

70

70

 

 

 

 

 

 

 

 

 

 

 

 

 

048100

2

5

 

NA

NA

NA

NA

NA

 

2-1/2

40

30

20

 

20

10

NA

 

060100

 

 

3

70

70

70

 

70

70

70

 

 

 

 

060120

2-1/2

10

 

NA

NA

NA

NA

NA

 

3*

70

70

70

 

70

70

70

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

ALTITUDE (FT)

UNIT SIZE

VENT PIPE

 

 

 

NUMBER OF 90° ELBOWS

 

 

DIAMETER (IN.)

 

1

 

2

3

 

4

5

6

 

 

 

 

 

 

024040

1-1/2

 

67

 

62

57

 

52

52

47

 

036040

2

 

70

 

70

70

 

70

70

70

 

 

 

 

 

 

 

 

 

 

 

 

 

024060

1-1/2

 

17

 

12

7

 

NA

NA

NA

 

036060

 

 

 

 

 

 

 

 

 

 

 

2

 

70

 

67

66

 

61

61

61

 

048060

 

 

 

2001 to 3000

 

 

 

 

 

 

 

 

 

 

 

036080

2

 

49

 

44

30

 

25

25

15

 

048080

 

 

 

 

 

 

 

 

 

 

 

2-1/2

 

70

 

70

70

 

70

70

70

 

060080

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

048100

2-1/2

 

35

 

26

16

 

16

6

NA

 

060100

3

 

70

 

70

70

 

70

66

61

 

 

 

 

 

 

 

 

 

 

 

 

 

060120

3*

 

63

 

62

62

 

61

61

61

 

 

 

 

 

 

 

 

 

 

 

ALTITUDE (FT)

UNIT SIZE

VENT PIPE

 

 

 

NUMBER OF 90° ELBOWS

 

 

DIAMETER (IN.)

 

1

 

2

3

 

4

5

6

 

 

 

 

 

 

024040

1-1/2

 

64

 

59

54

 

49

48

43

 

036040

2

 

70

 

70

70

 

70

70

70

 

024060

1-1/2

 

16

 

11

6

 

NA

NA

NA

 

036060

 

 

 

 

 

 

 

 

 

 

 

2

 

68

 

63

62

 

57

57

56

 

048060

 

 

 

3001 to 4000

036080

2

 

46

 

41

28

 

23

22

13

 

048080

 

 

 

 

 

 

 

 

 

 

 

2-1/2

 

70

 

70

70

 

70

70

70

 

060080

 

 

 

 

048100

2-1/2

 

33

 

24

15

 

14

5

NA

 

060100

3

 

70

 

70

70

 

66

61

56

 

 

 

 

 

 

 

 

 

 

 

 

 

060120

3*

 

59

 

59

58

 

57

57

56

 

 

 

 

 

 

 

 

 

 

 

ALTITUDE (FT)

UNIT SIZE

VENT PIPE

 

 

 

NUMBER OF 90° ELBOWS

 

 

DIAMETER (IN.)

 

1

 

2

3

 

4

5

6

 

 

 

 

 

 

024040

1-1/2

 

60

 

55

50

 

45

44

39

 

036040

2

 

70

 

70

70

 

70

70

70

 

024060

1-1/2

 

15

 

10

5

 

NA

NA

NA

 

036060

 

 

 

 

 

 

 

 

 

 

 

2

 

64

 

59

58

 

53

52

52

 

048060

 

 

 

4001 to 5000²

036080

2

 

44

 

39

26

 

21

20

11

 

048080

 

 

 

 

 

 

 

 

 

 

 

2-1/2

 

70

 

70

70

 

70

70

70

 

060080

 

 

 

 

048100

2-1/2

 

31

 

22

13

 

12

NA

NA

 

060100

3

 

70

 

70

67

 

62

57

52

 

060120

3*

 

56

 

55

54

 

53

52

52

* Wide radius elbow.

²Vent sizing for Canadian installations over 4500 ft (1370 m) above sea level are subject to acceptance by the local authorities having jurisdiction. NAÐNot Allowed; pressure switch will not make.

NOTES:

1. Do not use pipe size greater than those specified in table or incomplete combustion, flame disturbance, or flame sense lockout may occur.

2. Assume two 45° elbows equal one 90° elbow. Long radius elbows are desirable and may be required in some cases.

3. Elbows and pipe sections within the furnace casing and at the vent termination should not be included in vent length or elbow count.

4. The minimum pipe length is 5 ft for all applications.

Ð25Ð