Bryant 345MAV instruction manual Ð26Ð

Models: 345MAV

1 40
Download 40 pages 58.13 Kb
Page 26
Image 26

TABLE 4ÐMAXIMUM ALLOWABLE VENT PIPE LENGTH (FT) Continued

ALTITUDE (FT)

UNIT SIZE

VENT PIPE

 

 

NUMBER OF 90° ELBOWS

 

 

DIAMETER (IN.)

1

2

 

3

4

 

5

6

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

024040

1-1/2

57

52

 

47

42

 

40

35

 

036040

2

70

70

 

70

70

 

70

70

 

 

 

 

 

 

 

 

 

 

 

 

024060

1-1/2

14

9

 

NA

NA

 

NA

NA

 

036060

 

 

 

 

 

 

 

 

 

 

2

60

55

 

54

49

 

48

47

 

048060

 

 

5001 to 6000²

 

 

 

 

 

 

 

 

 

 

036080

2

41

36

 

23

18

 

17

8

 

048080

 

 

 

 

 

 

 

 

 

 

2-1/2

70

70

 

70

70

 

70

70

 

060080

 

 

 

 

 

 

 

 

 

 

 

 

 

 

048100

2-1/2

29

21

 

12

11

 

NA

NA

 

060100

3

70

67

 

62

57

 

52

47

 

060120

3*

53

52

 

50

49

 

48

47

 

 

 

 

 

 

 

 

 

 

 

ALTITUDE (FT)

UNIT SIZE

VENT PIPE

 

 

NUMBER OF 90° ELBOWS

 

 

DIAMETER (IN.)

1

2

 

3

4

 

5

6

 

 

 

 

 

024040

1-1/2

53

48

 

43

38

 

37

32

 

036040

2

70

70

 

68

67

 

66

64

 

024060

1-1/2

13

8

 

NA

NA

 

NA

NA

 

036060

 

 

 

 

 

 

 

 

 

 

2

57

52

 

50

45

 

44

43

 

048060

 

 

6001 to 7000²

 

 

 

 

 

 

 

 

 

 

036080

2

38

33

 

21

16

 

15

6

 

048080

 

 

 

 

 

 

 

 

 

 

2-1/2

70

70

 

68

67

 

66

64

 

060080

 

 

 

 

 

 

 

 

 

 

 

 

 

 

048100

2-1/2

27

19

 

10

9

 

NA

NA

 

060100

3

68

63

 

58

53

 

48

43

 

 

 

 

 

 

 

 

 

 

 

 

060120

3*

49

48

 

47

45

 

44

43

 

 

 

 

 

 

 

 

 

 

 

ALTITUDE (FT)

UNIT SIZE

VENT PIPE

 

 

NUMBER OF 90° ELBOWS

 

 

DIAMETER (IN.)

1

2

 

3

4

 

5

6

 

 

 

 

 

024040

1-1/2

49

44

 

39

34

 

33

28

 

036040

2

66

65

 

63

62

 

60

59

 

024060

1-1/2

12

7

 

NA

NA

 

NA

NA

 

036060

 

 

 

 

 

 

 

 

 

 

2

53

48

 

46

41

 

40

38

 

048060

 

 

7001 to 8000²

036080

2

36

31

 

19

14

 

12

NA

 

048080

 

 

 

 

 

 

 

 

 

 

2-1/2

66

65

 

63

62

 

60

59

 

060080

 

 

 

048100

2-1/2

25

17

 

8

7

 

NA

NA

 

060100

3

63

58

 

53

48

 

43

38

 

060120

3*

46

44

 

43

41

 

40

38

ALTITUDE (FT)

UNIT SIZE

VENT PIPE

 

 

NUMBER OF 90° ELBOWS

 

 

DIAMETER (IN.)

1

2

 

3

4

 

5

6

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

024040

1-1/2

46

41

 

36

31

 

29

24

 

036040

2

62

60

 

58

56

 

55

53

 

 

 

 

 

 

 

 

 

 

 

 

024060

1-1/2

11

6

 

NA

NA

 

NA

NA

 

036060

 

 

 

 

 

 

 

 

 

 

2

49

44

 

42

37

 

35

34

 

048060

 

 

8001 to 9000²

036080

2

33

28

 

17

12

 

10

NA

 

048080

 

 

 

 

 

 

 

 

 

 

2-1/2

62

60

 

58

56

 

55

53

 

060080

 

 

 

048100

2-1/2

23

15

 

7

5

 

NA

NA

 

060100

3

59

54

 

49

44

 

39

34

 

060120

3*

43

41

 

39

37

 

35

34

 

 

 

 

 

 

 

 

 

 

 

* Wide radius elbow.

²Vent sizing for Canadian installations over 4500 ft (1370 m) above sea level are subject to acceptance by the local authorities having jurisdiction. NAÐNot Allowed; pressure switch will not make.

NOTES:

1. Do not use pipe size greater than those specified in table or incomplete combustion, flame disturbance, or flame sense lockout may occur.

2. Assume two 45° elbows equal one 90° elbow. Long radius elbows are desirable and may be required in some cases.

3. Elbows and pipe sections within the furnace casing and at the vent termination should not be included in vent length or elbow count.

4. The minimum pipe length is 5 ft for all applications.

Ð26Ð

Page 26
Image 26
Bryant 345MAV instruction manual Ð26Ð