Bryant 345MAV ÐFactory-ShippedUpflow Tube Configuration, Shown With Blower Access Panel Removed

Models: 345MAV

1 40
Download 40 pages 58.13 Kb
Page 6
Image 6
Fig. 5ÐFactory-Shipped Upflow Tube Configuration

PLUG

 

CAP

 

COLLECTOR BOX

 

DRAIN TUBE (BLUE

 

& WHITE STRIPED)

 

COLLECTOR BOX

 

TUBE (PINK)

 

COLLECTOR BOX

 

TUBE (GREEN)

 

INDUCER HOUSING

 

(MOLDED) DRAIN

 

TUBE (BEHIND

 

COLLECTOR BOX

 

DRAIN TUBE)

 

COLLECTOR BOX

 

DRAIN TUBE (BLUE)

CONDENSATE

 

 

TRAP

FIELD-INSTALLED

 

FACTORY-SUPPLIED

 

DRAIN TUBE

 

COUPLING (LEFT

 

DRAIN OPTION)

 

PLUG

CAP

COLLECTOR BOX DRAIN TUBE (BLUE & WHITE STRIPED)

COLLECTOR BOX

TUBE (PINK)

COLLECTOR BOX

TUBE (GREEN)

COLLECTOR BOX DRAIN TUBE (BLUE)

CONDENSATE (Shown With Blower Access Panel Removed) TRAP

INDUCER HOUSING DRAIN TUBE (VIOLET)

FIELD-INSTALLED

 

FACTORY-SUPPLIED

 

DRAIN TUBE

 

FIELD-INSTALLED

FIELD-INSTALLED

FACTORY-SUPPLIED

FACTORY-SUPPLIED

12-IN. CPVC STREET

DRAIN TUBE

ELBOWS (2) FOR

COUPLING (RIGHT

LEFT DRAIN OPTION

DRAIN OPTION)

A94163

Fig. 5ÐFactory-Shipped Upflow Tube Configuration

(Shown With Blower Access Panel Removed)

D.Condensate Trap Tubing (Alternate Upflow Orientation)

NOTE: See Fig. 6 or tube routing label on main furnace door to confirm location of these tubes.

1. Collector Box Drain Tube

Connect collector box drain tube (blue label) to condensate trap.

NOTE: On 17-1/2-in. wide furnaces ONLY, cut tube between corrugated sections to prevent kinks from occurring.

2.Inducer Housing Drain Tube

a.Remove and discard LOWER (molded) inducer housing drain tube which was previously connected to conden- sate trap.

b.Use inducer housing drain extension tube (violet label and factory-supplied in loose parts bag) to connect LOWER inducer housing drain connection to the con- densate trap.

c.Determine appropriate length, cut, and connect tube.

d.Clamp tube to prevent any condensate leakage.

3.Relief Port Tube

a.Connect relief port tube (green label) to condensate trap.

b.Use smaller diameter tube (factory-supplied in loose parts bag) to extend this tube if required.

Ð6Ð

A94164

Fig. 6ÐAlternate Upflow Tube Configuration and

Trap Location

c.Determine appropriate length, cut, and connect tube.

E. Condensate Trap Field Drain Attachment

Refer to Condensate Drain section for recommendations and procedures.

F. Pressure Switch Tubing

The LOWER collector box pressure tube (pink label) is factory connected to the pressure switch and should not require any modification.

NOTE: See Fig. 5 or 6 or tube routing label on main furnace door to check for proper connections.

G.Upper Collector Box and Inducer Housing (Unused) Drain Connections

UPPER COLLECTOR BOX DRAIN CONNECTION

Attached to the UPPER collector box drain connection is a factory-installed corrugated, plugged tube (blue and white striped label). This tube is plugged to prevent condensate leakage in this application. Ensure this tube is plugged.

NOTE: See Fig. 5 or 6 or tube routing label on main furnace door to check for proper connections.

UPPER INDUCER HOUSING DRAIN CONNECTION

Attached to the UPPER (unused) inducer housing drain connection is a cap and clamp. This cap is used to prevent condensate leakage in this application. Ensure this connection is capped.

Page 6
Image 6
Bryant 345MAV ÐFactory-ShippedUpflow Tube Configuration, Shown With Blower Access Panel Removed, Trap Location