Fig. 32ÐShort Vent (5 to 8 Ft) System

TABLE 4ÐMAXIMUM ALLOWABLE VENT PIPE LENGTH (FT) Continued

ALTITUDE (FT)

UNIT SIZE

VENT PIPE

 

 

NUMBER OF 90° ELBOWS

 

 

DIAMETER (IN.)

1

2

 

3

4

 

5

6

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

024040

1-1/2

42

37

 

32

27

 

25

20

 

036040

2

57

55

 

53

51

 

49

47

 

 

 

 

 

 

 

 

 

 

 

 

024060

 

 

 

 

 

 

 

 

 

 

036060

2

45

40

 

38

33

 

31

29

 

048060

 

 

 

 

 

 

 

 

 

9001 to 10,000²

036080

2

30

25

 

14

9

 

7

NA

 

048080

 

 

 

 

 

 

 

 

 

 

2-1/2

57

55

 

53

51

 

49

47

 

060080

 

 

 

 

 

 

 

 

 

 

 

 

 

 

048100

2-1/2

21

13

 

5

NA

 

NA

NA

 

060100

3

54

49

 

44

39

 

34

29

 

060120

3*

39

37

 

35

33

 

31

29

 

 

 

 

 

 

 

 

 

 

 

* Wide radius elbow.

²Vent sizing for Canadian installations over 4500 ft (1370 m) above sea level are subject to acceptance by the local authorities having jurisdiction. NAÐNot Allowed; pressure switch will not make. NOTES:

1. Do not use pipe size greater than those specified in table or incomplete combustion, flame disturbance, or flame sense lockout may occur.

2. Assume two 45° elbows equal one 90° elbow. Long radius elbows are desirable and may be required in some cases.

3. Elbows and pipe sections within the furnace casing and at the vent termination should not be included in vent length or elbow count.

4. The minimum pipe length is 5 ft for all applications.

Ð27Ð12MIN Manual background

Manual background 12MIN Manual background

VENT PIPE

 

 

VENT PIPE

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

HORIZONTAL TO ROOF

HORIZONTAL TO SIDEWALL

 

VENT PIPE

 

12MIN

 

12MIN

 

VENT PIPE

VERTICAL TO ROOF

VERTICAL TO SIDEWALL

NOTE: A 12-In. minimum offset pipe section is recommended with short (5 to 8 ft) vent systems. This recommendation is to reduce excessive condensate droplets from exiting the vent pipe.

A96189

Fig. 32ÐShort Vent (5 to 8 Ft) System