Bryant 345MAV Ðmaximum Capacity Of Pipe Cu Ft Per Hr, ÐTypical Gas Pipe Arrangement

Models: 345MAV

1 40
Download 40 pages 58.13 Kb
Page 19
Image 19
TABLE 2ÐMAXIMUM CAPACITY OF PIPE

TABLE 2ÐMAXIMUM CAPACITY OF PIPE

(CU FT PER HR)*

NOMINAL

 

 

LENGTH OF PIPE (FT)

 

IRON

INTERNAL

 

 

 

 

 

 

 

 

PIPE

DIAMETER

 

 

 

 

 

 

 

 

 

 

 

 

SIZE

(IN.)

10

 

20

30

40

50

(IN.)

 

 

 

 

 

 

 

 

 

1/2

0.622

175

 

120

97

82

73

3/4

0.824

360

 

250

200

170

151

1

1.049

680

 

465

375

320

285

1-1/4

1.380

1400

 

950

770

660

580

1-1/2

1.610

2100

 

1460

1180

990

900

 

 

 

 

 

 

 

 

CAUTION: If a flexible connector is required or al- lowed by authority having jurisdiction, black iron pipe shall be installed at gas valve and extend a minimum of 2 in. outside furnace casing.

An accessible manual shutoff valve MUST be installed upstream of furnace gas controls and within 6 ft of furnace. A 1/8-in. NPT plugged tapping, accessible for test gage connection, MUST be installed immediately upstream of gas supply connection to furnace and downstream of manual shutoff valve.

*For gas pressures of 0.5 psig (14-in. wc) or less, and a pressure drop of 0.5-in. wc (based on a 0.60 specific gravity gas). Ref: Table 10-2 NFGC .

GASFig. 23ÐTypical Gas Pipe ArrangementELECTRICAL CONNECTIONSManual background

SUPPLY

MANUAL Manual background

SHUTOFF

VALVE Manual backgroundManual backgroundManual backgroundManual backgroundManual backgroundManual backgroundManual backgroundManual backgroundManual backgroundManual background (REQUIRED) Manual backgroundManual backgroundManual background

SEDIMENT

TRAP

UNION

A93324

Fig. 23ÐTypical Gas Pipe Arrangement

NOTE: The gas valve inlet press tap connection is suitable to use as test gage connection providing test pressure DOES NOT exceed maximum 0.5 psig (14-in. wc) stated on gas valve. (See Fig. 40.) Piping should be pressure tested in accordance with local and national plumbing and gas codes before furnace is attached. In Canada, refer to current edition of NSCNGPIC. If pressure exceeds 0.5 psig (14-in. wc), gas supply pipe must be disconnected from furnace and capped before pressure test. If test pressure is equal to or less than 0.5 psig (14-in. wc), turn off electric shutoff switch located on gas valve before test. It is recommended that ground joint union be loosened before pressure testing. After all connections have been made, purge lines and check for leakage.

ELECTRICAL CONNECTIONS

See Fig. 24 for field wiring diagram showing typical field 115-v and 24-v wiring. Check all factory and field electrical connections for tightness.

WARNING: Blower access panel door switch opens 115-v power to control center. No component operation can occur. Do not bypass or close switch with panel removed. Failure to follow this warning could result in personal injury or death.

FIELD 24-V WIRING

FIELD 115-, 208/230-, 460-V WIRING

FACTORY 24-V WIRING

FACTORY 115-V WIRING

 

 

 

NOTE 2

 

 

 

THERMOSTAT

 

 

 

FIVE

 

W C R

G

Y

FIELD-SUPPLIED

 

 

 

TERMINALS

 

 

 

 

 

 

 

 

WIRE

 

 

 

 

 

DISCONNECT

 

 

THREE-WIRE

 

 

 

 

 

208/230- OR

 

 

HEATING-

 

 

 

 

 

 

 

ONLY

 

 

 

 

 

460-V

 

 

 

 

 

 

 

 

THREE

BLK

BLK

 

W

 

 

 

 

PHASE

 

 

 

 

 

 

 

 

 

 

 

 

 

WHT

WHT

 

R

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

208/230-V

 

GND

GND

 

 

 

 

 

SINGLE

 

115-V

AUXILIARY

G

 

 

 

 

PHASE

 

 

 

 

 

 

 

FIELD-SUPPLIED

J-BOX

C

NOTE 1

 

 

 

GND

DISCONNECT

CONTROL

Y

 

 

CONDENSING

 

 

BOX

 

 

 

UNIT

 

 

 

 

 

 

 

 

 

 

 

 

24-V

 

 

 

TWO

 

 

 

TERMINAL

 

 

 

WIRE

 

 

 

 

BLOCK

NOTES: 1.

Connect Y-terminal as shown for proper operation.

 

 

FURNACE

 

 

 

2.￿ Some thermostats require a "C" terminal connection as shown.

 

 

 

 

 

3.If any of the original wire, as supplied, must be replaced, use same type or equivalent wire.

A98209

Fig. 24ÐHeating and Cooling Application Wiring Diagram

Ð19Ð

Page 19
Image 19