Mechanical Cooling Lockout
Determine the
Dry Bulb Changeover Set Up
Determine the dry bulb changeover set point from Table 4. The settings are A, B, C and D. Locate the ECON SP potenti- ometer and set the dry bulb changeover set point. See Fig. 34. When the OAT is above this set point, the damper is limited to minimum position setting.
Table 4 — Changeover Set Points
SETTINGS | A | B | C | D | |
Dry Bulb (°F) | 73 | 69 | 66 | 63 | |
Single Enthalpy* (Btu/lb) | 27 | 25 | 24 | 22 | |
Differential Temperature* | 2 | 2 | 2 | 2 | |
(°F, Not Adjustable) | |||||
|
|
|
| ||
Differential Enthalpy* | 1 | 1 | 1 | 1 | |
(Btu/lb, Not Adjustable) | |||||
|
|
|
| ||
|
|
|
|
If a potentiometer fails, its setting will default to the values in Table 5.
Table 5 — Default Potentiometer Settings
POTENTIOMETER | DEFAULT SETTING |
CO2 SP (PPM) | 1,000 |
MECH CLG LOCKOUT | 47° |
ECON SP | D |
MIN POS (%) | 20 |
Ventilation Air (Minimum Position Set Up)
If ventilation air is not required, proceed to Step 5. If ventila- tion air is required, perform the following:
1.The indoor fan must be on to set the ventilation air. Either put the thermostat in the continuous fan mode or jumper the R and G terminals at the rooftop unit connection board.
2.Locate the minimum position (MIN POS) potentiome- ter. Turn the potentiometer full CCW to fully close the outdoor air dampers. Turn the potentiometer gradually clockwise (CW) to the desired position. See Fig. 34.
3.Replace the filter access panel. See Fig. 11. Ensure the filter access panel slides along the tracks and is securely engaged.
4.Calculate the minimum airflow across the EconoMi$er.
a.Calculate % of outside air using the following formula.
%Outdoor air through EconoMi$er
%Outdoor air = Mixture Temp – Return Air Temp Outdoor Temp – Return Air Temp
b.Divide total CFM by percentage outdoor air, this gives outdoor air volume in CFM.
5.Turn on base unit power.
NOTE: The EconoMi$er begins operation three minutes after power up.
WARNING: PERSONAL INJURY HAZARD. Avoid possible injury by keeping fingers away from damper blades.
See Fig. 35 for barometric relief damper characteristics.
Fig. 34 — EconoMi$er Control Adjustment
Potentiometers (Factory Settings)
WG) | 0.5 |
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
| ||
0.4 |
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
| |
(IN. |
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
| |
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
| ||
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
| |
PRESSURE | 0.3 |
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
| |
| 0.2 |
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
| |
STATIC | 0.1 |
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
| ||
0 |
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
| |
|
| 200 | 400 | 600 | 800 | 1000 | 1200 | 1400 | 1600 | |||||||||
| 0 | |||||||||||||||||
|
|
|
|
| FLOW (CUBIC FEET/MINUTE) |
|
|
|
| |||||||||
| Fig. 35 — Barometric Relief Capacity |
|
|
VII. STEP 7 — ADJUST INDOOR-FAN SPEED
Adjust
For units with electric heat, required minimum cfm is 2250 for 548D090, 2550 for 548D102 and 3000 for 548D120 with the following exceptions:
| UNIT | HEATER | UNIT | REQUIRED | |
UNIT | CONFIG- | MINIMUM | |||
VOLTAGE | kW | ||||
| URATION | CFM | |||
|
|
| |||
| 208/230 | 42.4 | Horizontal | 3200 | |
| 208/230 | 50.0 | Horizontal | 3200 | |
|
|
| Horizontal |
| |
548D120 | 460 | 50.0 | or | 3200 | |
|
|
| Vertical |
| |
|
| 17.0 | Horizontal | 2800 | |
| 575 | 51.0 | or | 2350 | |
|
| Vertical | |||
|
|
|
|
Table 6 shows
To change fan speeds:
1.Shut off unit power supply and tag disconnect.
2.Loosen belt by loosening fan motor mounting nuts See Fig. 36 and 37.
3.Loosen movable pulley flange setscrew (see Fig. 38).
4.Screw movable flange toward fixed flange to increase fan rpm or away from fixed flange to decrease speed. Increasing fan rpm increases load on motor. Do not
exceed maximum speed specified in Table 1.