Bryant 548D installation instructions

Models: 548D

1 40
Download 40 pages 47.2 Kb
Page 26
Image 26
—26—

Table 12 — Fan Performance 548D102 — Horizontal Discharge Units

STANDARD MOTOR (BELT DRIVE)

Airflow

 

 

 

 

 

External Static Pressure (in. wg)

 

 

 

 

 

 

 

0.2

 

 

0.4

 

 

0.6

 

 

0.8

 

 

1.0

 

 

(Cfm)

 

 

 

 

 

 

 

 

 

 

 

 

Rpm

Bhp

Watts

Rpm

Bhp

Watts

Rpm

Bhp

Watts

Rpm

Bhp

Watts

Rpm

Bhp

Watts

 

2550

501

0.57

577

587

0.79

747

659

1.05

956

722

1.29

1156

780

1.55

1378

 

2660

507

0.59

592

592

0.82

771

663

1.08

981

727

1.32

1182

784

1.58

1404

 

2700

520

0.65

638

604

0.89

827

672

1.14

1031

737

1.40

1250

793

1.66

1473

 

2800

533

0.71

684

615

0.95

875

683

1.20

1081

747

1.49

1327

802

1.75

1552

 

2900

546

0.77

731

626

1.02

932

693

1.27

1140

756

1.57

1396

813

1.84

1630

 

3000

559

0.83

779

637

1.09

989

704

1.35

1207

765

1.66

1473

823

1.94

1718

 

3100

572

0.90

835

648

1.17

1056

715

1.43

1275

775

1.74

1543

832

2.05

1814

 

3200

585

0.96

883

660

1.24

1114

727

1.52

1353

785

1.83

1321

841

2.15

1901

 

3300

598

1.03

940

671

1.32

1182

739

1.62

1439

795

1.91

1691

851

2.26

1997

 

3400

610

1.10

998

682

1.41

1258

750

1.72

1526

806

2.01

1779

860

2.36

2084

 

3500

623

1.17

1056

694

1.50

1335

761

1.82

1613

817

2.11

1866

870

2.47

2180

 

3600

636

1.25

1123

707

1.60

1422

772

1.93

1709

828

2.23

1971

880

2.57

2266

 

3700

649

1.33

1190

720

1.71

1517

783

2.03

1796

840

2.35

2076

890

2.69

2369

 

3750

655

1.37

1224

727

1.77

1569

789

2.09

1849

846

2.42

2136

896

2.75

2420

 

3800

661

1.41

1258

733

1.82

1613

795

2.15

1901

852

2.48

2188

901

2.80

2462

 

3900

674

1.49

1327

746

1.93

1709

806

2.26

1997

863

2.61

2300

912

2.93

2571

 

4000

687

1.57

1396

759

2.05

1814

817

2.38

2102

874

2.75

2420

923

3.08

2694

 

4100

699

1.60

1473

772

2.17

1919

828

2.50

2206

885

2.88

2529

935

3.23

2815

 

4200

712

1.75

1552

785

2.30

2032

840

2.64

2326

897

3.03

2653

947

3.39

2940

 

4250

719

1.80

1595

792

2.37

2093

846

2.71

2386

903

3.10

2710

 

 

 

 

 

 

 

 

 

 

 

 

 

 

STANDARD MOTOR (BELT DRIVE) (cont)

 

 

 

 

 

 

 

 

 

 

 

 

Airflow

 

 

 

 

 

External Static Pressure (in. wg)

 

 

 

 

 

 

 

1.2

 

 

1.4

 

 

1.6

 

 

1.8

 

 

2.0

 

 

(Cfm)

 

 

 

 

 

 

 

 

 

 

 

 

Rpm

Bhp

Watts

Rpm

Bhp

Watts

Rpm

Bhp

Watts

Rpm

Bhp

Watts

Rpm

Bhp

Watts

 

2550

836

1.83

1621

887

2.13

1884

931

2.45

2162

964

2.77

2436

986

3.11

2718

 

2660

839

1.87

1656

891

2.17

1919

936

2.49

2197

973

2.82

2479

999

3.16

2759

 

2700

846

1.95

1726

898

2.26

1997

946

2.58

2275

987

2.91

2554

1019

3.26

2839

 

2800

855

2.04

1805

906

2.35

2076

954

2.67

2352

997

3.01

2637

1034

3.36

2917

 

2900

863

2.13

1884

913

2.44

2154

961

2.77

2436

1006

3.12

2727

 

3000

872

2.22

1962

921

2.54

2240

969

2.88

2529

1014

3.22

2807

 

3100

882

2.33

2058

930

2.65

2335

976

2.99

2620

1021

3.34

2902

 

3200

892

2.45

2162

939

2.76

2428

984

3.10

2710

 

3300

902

2.57

2266

948

2.88

2529

993

3.21

2799

 

3400

912

2.69

2369

958

3.01

2637

1002

3.34

2902

 

3500

921

2.82

2479

968

3.15

2751

 

3600

930

2.95

2587

978

3.29

2862

 

3700

940

3.07

2686

 

3750

945

3.14

2743

 

3800

949

3.20

2781

 

3900

959

3.33

2894

 

4000

 

4100

 

4200

 

4250

 

LEGEND

Bhp — Brake Horsepower Input to Fan

Watts — Input Watts to Motor

NOTES:

1.Boldface indicates field-supplied drive is required. (See Note 6.)

2.Manual backgroundManual background indicates field-supplied motor and drive are required.

3.Maximum usable watts input is 2120 and maximum continuous bhp is 2.40. Extensive motor and electrical testing on these units ensures that the full range of the motor can be utilized with

confidence. Using your fan motors up to the wattage ratings shown will not result in nuisance tripping or premature motor failure. Unit warranty will not be affected.

4.Values include losses for filters, unit casing, and wet coils.

5.Use of a field-supplied motor may affect wire sizing. Contact your representative to verify.

6.Standard motor drive range: 685 to 935 rpm. All other rpms require field-supplied drive.

7.Interpolation is permissible. Do not extrapolate.

26

Page 26
Image 26