D. Cooling, Units With EconoMi$er
When the Outdoor Air Temperature (OAT) is above the ECON SP set point and the room thermostat calls for Stage 1 cooling (R to G + Y1), the
When the OAT is below the ECON SP setting and the room thermostat calls for Stage 1 cooling (R to G + Y1), the EconoMi$er modulates to the minimum position when the IFM is energized. The EconoMi$er provides Stage 1 of cool- ing by modulating the return and
If outdoor air alone cannot satisfy the cooling requirements of the conditioned space, and the OAT is above the MECH CLG LOCKOUT set point, the EconoMi$er integrates free cooling with mechanical cooling. This is accomplished by the strategies below.
NOTE: Compressors have a
1.If Y1 is energized, and the room thermostat calls for Y2
2.If Y1 is energized for more then 20 minutes, and Y2 is not energized (whether or not a
3.If Y1 is energized, and compressor no. 1 is already energized and the room thermostat calls for Y2, compressor no. 1 continues to operate. If Y2 remains energized for more than 20 minutes, compressor no. 2 is energized.
NOTE: Compressor no. 2 cannot be energized unless there is a signal for Y2 from the space thermostat.
4.If compressor no. 2 is energized, and the Y2 signal from the thermostat is satisfied, compressor no. 1 and 2 are deenergized.
5.If compressor no. 1 is energized and the thermostat is satisfied, compressor no. 1, the OFM, and IFM are deenergized and the EconoMi$er modulates closed.
When the OAT is below the MECH CLG LOCKOUT set point, the compressors remain off.
E.Heating, Units With Economizer (If Accessory Heater is Installed)
When the room thermostat calls for heat through terminal W1, the
energized through W2. The
F. Defrost
When the temperature of the outdoor coil drops below 28 F as sensed by the defrost thermostat (DFT2) and the defrost timer is at the end of a timed period (adjustable at 30, 50, or 90 minutes), reversing valve solenoids (RVS1 and RVS2) are energized and the OFC is deenergized. This switches the position of the reversing valves and shuts off the outdoor fans. The electric heaters (if installed) will be energized.
The unit continues to defrost until the coil temperature as measured by DFT2 reaches 65 F, or the duration of defrost cycle completes a
During the defrost mode, if circuit 1 defrosts first, RVS1 will oscillate between heating and cooling modes until the defrost mode is complete.
At the end of the defrost cycle, the electric heaters (if in- stalled) will be deenergized; the reversing valves switch and the
If the space thermostat is satisfied during a defrost cycle, the unit will continue in the defrost mode until the time or tem- perature constraints are satisfied.
SERVICE
CAUTION: When servicing unit, shut off all elec- trical power to unit and install lock out tag to avoid shock hazard or injury from rotating parts.
I. CLEANING
Inspect unit interior at the beginning of each heating and cooling season or more frequently as operating conditions require.
A.Indoor Coil
1.Turn unit power off and tag disconnect. Remove filter access panel and indoor coil access panel.
2.If economizer or accessory
3.Slide filters out of unit.
4.Clean coil using a commercial coil cleaner or dish- washer detergent in a pressurized spray canister. Wash both sides of coil and flush with clean water. For best results, backflush toward
5.Flush condensate pan after completion.
6.Reinstall
7.Reconnect wiring.
8.Replace access panels.