Bryant 548D V. - Make Electrical Connections, A. Field Power Supply, Power Wiring Connections

Models: 548D

1 40
Download 40 pages 47.2 Kb
Page 7
Image 7
V. STEP 5 — MAKE ELECTRICAL CONNECTIONS

V. STEP 5 — MAKE ELECTRICAL CONNECTIONS

A. Field Power Supply WARNING: Unit cabinet must have an uninter- rupted, unbroken electrical ground to minimize the possibility of personal injury if an electrical fault should occur. This ground may consist of electrical wire connected to unit ground lug in control compartment, or conduit approved for electrical ground when installed in accordance with NEC (National Electrical Code) ANSI (American National Standards Institute) / NFPA (National Fire Protection Association) 70 latest year and local electrical codes. Failure to follow this warning could result in the installer being liable for personal injury of others.

A. Field Power Supply

All units except 208/230-v units are factory-wired for the voltage shown on the unit nameplate. If the 208/230-v unit is to be connected to a 208-v power supply, the transformer must be rewired by disconnecting the black wire from the 230-v terminal on the transformer and connecting it to the 200-v terminal from the transformer.

Refer to unit label diagram for additional information. Pig- tails are provided for field wire connections. Use factory- supplied splices or UL (Underwriters’ Laboratories) approved copper/aluminum connector.

When installing units, provide a disconnect per the NEC.

All field wiring must comply with the NEC and local re- quirements. In Canada, electrical connections must be made in accordance with CSA (Canadian Standards Association) C22.1 Canadian Electrical Code Part One.

Install field wiring as follows:

1.Install conduit through side panel openings. For units without electric heat, install conduit between discon- nect and control box.

2.Install power lines to terminal connections as shown in Fig. 7.

3.For units with electric heat, refer to Accessory Instal- lation Instructions.

4.If thru-the-bottom control connections are used, refer to the accessory installation instructions for informa- tion on control wiring. Refer to Fig. 6 for drilling holes in basepan.

During operation, voltage to compressor terminals must be within range indicated on unit nameplate (see Tables 2A and 2B). On 3-phase units, voltages between phases must be bal- anced within 2%, and the current within 10%. Use the for- mula shown in Tables 2A and 2B, Note 2 on page 10 to determine the percentage of voltage imbalance. Operation on improper line voltage or excessive phase imbalance consti- tutes abuse and may cause damage to electrical compo- nents. Such operation would invalidate any applicable warranty.

208/230-3-60

 

LEGEND

575-3-60

460-3-60

 

 

C

Contactor

 

 

 

 

COMP — Compressor

 

 

IFC

Indoor Fan Contactor

 

 

NEC

National Electrical Code

 

 

TB

Terminal Block

 

 

 

Field Wiring

 

Factory Wiring Splice Connection (Factory-Supplied)

Fig. 7 — Power Wiring Connections

7

Page 7
Image 7
Bryant 548D installation instructions V. - Make Electrical Connections, A. Field Power Supply, Power Wiring Connections