MAXIMUM ALLOWABLE
DIFFERENCE (in.)
0.5 | 1.0 | 1.0 |
Fig. 2 — Unit Leveling Tolerances
II. STEP 2 — FIELD FABRICATE DUCTWORK
On vertical discharge units, secure all ducts to roof curb and building structure. Do not connect ductwork to unit. For hori- zontal applications,
Ducts passing through an unconditioned space must be insu- lated and covered with a vapor barrier.
If a plenum return is used on a vertical unit, the return should be ducted through the roof deck to comply with ap- plicable fire codes.
A minimum clearance to combustibles is not required around ductwork on vertical discharge units. On horizontal discharge units with electric heat, a minimum clearance of 1 in. is required for the first 12 in. of ductwork. Cabinet
CAUTION: Ensure voltage listed on unit data plate agrees with electrical supply provided for the unit.
III.STEP 3 — INSTALL CONDENSATE DRAIN LINE AND EXTERNAL TRAP
Condensate drain connections are located on the bottom and end of the unit. Unit discharge connections do not determine the use of drain connections; either drain connection can be used in vertical or horizontal applications.
When using the standard end drain connection, make sure the plug (Red) in the alternate bottom connection is tight before installing the unit.
To use the bottom drain connection for a roof curb installa- tion, relocate the
All units must have an external trap for condensate drain- age. Install a trap at least
IV. STEP 4 — RIG AND PLACE UNIT
Inspect unit for transportation damage. File any claim with transportation agency. Keep unit upright and do not drop. Spreader bars are not required if top crating is left on unit. Rollers may be used to move unit across a roof. Level by using unit frame as a reference. See Table 1 and Fig. 5 for additional information. Operating weight is shown in Table 1 and Fig. 5.
Lifting holes are provided in base rails as shown in Fig. 5 and 6. Refer to rigging instructions on unit.
Positioning
Maintain clearance around and above unit to provide proper airflow and service access. See Fig. 6.
Position unit on roof curb so that the following clearances are maintained:
Do not install unit in an indoor location. Do not locate unit air inlet near exhaust vents or other sources of contami- nated air.
Although unit is weatherproof, guard against water from higher level runoff and overhangs.
After unit is in position, remove polyethylene shipping wrap- per and rigging skid.
DRAIN PLUG
NOTE: Drain plug is shown in
Fig. 3 — Condensate Drain Connection
NOTE: Trap should be deep enough to offset maximum unit static dif- ference. A