Bryant 548D installation instructions Physical Data

Models: 548D

1 40
Download 40 pages 47.2 Kb
Page 6
Image 6

Table 1 — Physical Data

UNIT SIZE 548D

 

090

 

102

 

120

NOMINAL CAPACITY (tons)

 

71/2

 

81/2

 

10

OPERATING WEIGHT (lb)

 

 

 

 

 

 

Unit

 

 

 

 

 

 

Al/Al*

 

940

 

965

 

1015

Economizer

 

 

 

 

 

 

Durablade

 

44

 

44

 

44

EconoMi$er

 

62

 

62

 

62

Roof Curb†

 

143

 

143

 

143

COMPRESSOR

 

 

 

Hermetic Scroll

 

 

Quantity

 

2

 

2

 

2

 

 

 

Oil (oz)

 

45 ea

 

62 ea

 

54 ea

REFRIGERANT TYPE

 

 

 

R-22

 

 

Operating Charge (lb-oz)

 

 

 

 

 

 

 

 

 

 

 

 

Circuit 1

 

5-14

 

8- 6

 

7-14

Circuit 2

 

5-13

 

8-13

 

8- 3

OUTDOOR COIL

 

Enhanced Copper Tubes, Aluminum Lanced Fins, Acutrol™ Feed Device

Rows...Fins/in.

 

1...17

 

2...17

 

2...17

 

 

 

Total Face Area (sq ft)

 

20.50

 

18.00

 

18.30

OUTDOOR FAN

 

 

 

Propeller Type

 

 

Nominal Cfm

 

6500

 

6500

 

6500

 

 

 

Quantity...Diameter (in.)

 

2...22

 

2...22

 

2...22

Motor Hp...Rpm

 

1/4...1100

 

1/4...1100

 

1/4...1100

Watts Input (Total)

 

600

 

600

 

600

INDOOR COIL

 

Enhanced Copper Tubes, Aluminum Double-Wavy Fins, Acutrol Fixed Orifice Metering Feed Device

Rows...Fins/in.

 

3...15

 

3...15

 

3...15

 

 

 

Total Face Area (sq ft)

 

8.0

 

8.0

 

11.1

INDOOR FAN

 

 

 

Centrifugal Type

 

 

Quantity...Size (in.)

Std

1...15 x 15

 

1...15 x 15

 

1...15 x 15

 

 

 

Alt

1...15 x 15

 

 

1...15 x 15

Type Drive

Std

Belt

 

Belt

 

Belt

Nominal Cfm

Alt

Belt

 

 

Belt

 

3000

 

3600

 

4000

Maximum Continuous Bhp

Std

2.40

 

2.40

 

2.40

 

Alt

 

 

2.90

Motor Frame Size

Std

56

 

56

 

56

 

Alt

 

 

56

Nominal Rpm High/Low

Std

 

 

 

Alt

 

 

Fan Rpm Range

Std

590-840

 

685-935

 

685- 935

Motor Bearing Type

Alt

685-935

 

 

835-1085

 

Ball

 

Ball

 

Ball

Maximum Allowable Rpm

 

2100

 

2100

 

2100

Motor Pulley Pitch Diameter Min/Max (in.)

Std

2.4/3.4

 

2.8/3.8

 

2.8/3.8

 

Alt

2.8/3.8

 

 

3.4/4.4

Nominal Motor Shaft Diameter (in.)

Std

5/8

 

5/8

 

5/8

 

Alt

 

 

7/8

Fan Pulley Pitch Diameter (in.)

Std

7.0

 

7.0

 

7.0

 

Alt

7.0

 

 

7.0

Belt, Quantity...Type...Length (in.)

Std

1...A...48

 

1...A...48

 

1...A...48

 

Alt

1...A...48

 

 

1...A...48

Pulley Center Line Distance (in.)

Std

16.75-19.25

 

16.75-19.25

 

15.85-17.50

Speed Change per Full Turn of

Alt

15.75-19.25

 

 

15.85-17.50

 

 

 

 

 

 

Movable Pulley Flange (rpm)

Std

50

 

50

 

50

Movable Pulley Maximum Full Turns

Alt

50

 

 

50

 

 

 

 

 

 

From Closed Position

Std

5

 

5

 

5

 

Alt

5

 

 

5

Factory Setting

Std

5

 

5

 

5

 

Alt

5

 

 

5

Factory Speed Setting (rpm)

Std

590

 

685

 

685

Fan Shaft Diameter at Pulley (in.)

Alt

685

 

 

835

 

1

 

1

 

1

HIGH-PRESSURE SWITCH (psig)**

 

 

 

 

 

 

Standard Compressor Internal Relief (Differential)

 

450 ± 50

 

 

Cutout

 

 

428

 

 

Reset (Auto.)

 

 

320

 

 

LOSS-OF-CHARGE SWITCH (psig)**

 

 

 

 

 

 

Cutout

 

 

7 ± 3

 

 

Reset (Auto.)

 

 

22 ± 5

 

 

FREEZE-PROTECTION THERMOSTAT (F)**

 

 

 

 

 

 

Opens

 

 

30 ± 5

 

 

Closes

 

 

45 ± 5

 

 

OUTDOOR-AIR INLET SCREENS

 

 

 

Cleanable

 

 

Quantity...Size (in.)

 

 

 

1...20 x 25 x 1

 

 

 

 

 

 

1...16 x 25 x 1

 

 

RETURN-AIR FILTERS

 

 

 

Throwaway

 

 

Quantity...Size (in.)

 

4...16 x 20 x 2

 

4...16 x 20 x 2

 

4...20 x 20 x 2

 

 

 

LEGEND

Al — Aluminum

Bhp — Brake Horsepower

*Indoor coil fin material/outdoor coil fin material. †Weight of 14-in. roof curb.

**Requires an accessory or optional controls upgrade kit.

NOTE: The 548D units have a loss-of-charge switch located in the liquid line avail- able as an option or an accessory. (Standard on 120 units.)

6

Page 6
Image 6
Bryant 548D installation instructions Physical Data