165
SOUND DATA
LEGEND

ARI Air Conditioning and Refrigeration Institute

NOTE: Indoor sound power is available in Bryant’s Electronic Catalog Program (ECAT) for

specific operating parameters.

PERFORMANCE DATA — 581C

581C024-036

LEGEND
*The values listed in this table do not include power exhaust. See table at right
for power exhaust requirements.
**Fuse or HACR circuit breaker.
†460v motor
NOTES:
1. In compliance with NEC requirements for multimotor and combination load
equipment (refer to NEC Articles 430 and 440), the overcurrent protective
device for the unit shall be fuse or HACR breaker. The UL, Canada units
may be fuse or circuit breaker.
2. Electrical data based on 95 F ambient outdoor-air temperature ± 10%
voltage.
3. Unbalanced 3-Phase Supply Voltage
Never operate a motor where a phase imbalance in supply voltage is
greater than 2%. Use the following formula to determine the percent of volt-
age imbalance.
Example: Supply voltage is 460-3-60.
AB = 452 v
BC = 464 v
AC = 455 v
Determine maximum deviation from average voltage.
(AB) 457 – 452 = 5 v
(BC) 464 – 457 = 7 v
(AC) 457 – 455 = 2 v
Maximum deviation is 7 v.
Determine percent of voltage imbalance.
This amount of phase imbalance is satisfactory as it is below the maximum
allowable 2%.
POWER EXHAUST ELECTRICAL DATA
* — Single or three phase rooftop unit
N/A — Not available
NOTE: If a single power source is to be used, size wire to include power
exhaust MCA and MOCP.
Check MCA and MOCP when power exhaust is powered through the unit.
Determine the new MCA including the power exhaust using the following
formula:
MCA New = MCA unit only + MCA of Power Exhaust
For example, using a 581B060—unit with MCA = 28.9 and MOCP = 35, with
CRPWREXH030A01 power exhaust.
MCA New = 28.9 amps + 1.6 amps = 30.5 amps
If the new MCA does not exceed the published MOCP, then MOCP would
not change. The MOCP in this example is 35 amps and the MCA New is
below 35; therefore the MOCP is acceptable. If “MCA New” is larger than
the published MOCP, raise the MOCP to the next larger size. For separate
power, the MOCP for the power exhaust will be 15 amps per NEC.

UNIT

581C

ARI

RATING

(decibels)

A-WEIGHTED

(db)

OCTAVE BANDS

63 125 250 500 1000 2000 4000 8000

024-048 76 76.0 55.9 66.0 64.0 66.2 68.4 64.5 61.7 57.3

060 80 80.0 59.1 68.9 68.7 71.9 74.0 68.9 65.7 59.0

UNIT
SIZE NOMINAL
V-PH-Hz IFM TYPE VOLTAGE
RANGE COMPRESSOR OFM COMBUSTION
FAN MOTOR IFM CONV
OUTLET
POWER SUPPLY
*
MINIMUM UNIT
DISCONNECT
SIZE
Min Max QTY RLA LRA QTY FLA FLA FLA MCA MOCP
** FLA LRA
024
(2 tons) 208/
230-1-60 STD 187 254 1 10.9 63 1 0.7 0.6 2.0 NO 16.3 20 15.6 69
YES 22.3 25 21.2 73
036
(3 tons)
208/
230-1-60 STD 187 254 1 16 88 1 0.7 0.6 4.9 NO 25.6 30 24.8 101
YES 31.6 35 30.4 106
208/
230-3-60
STD
187 254 1 10.3 77 1 0.7 0.6
4.9 NO 18.5 25 18.3 90
YES 24.5 30 23.8 95
HS 5.8 NO 19.4 25 19.3 120
YES 25.4 30 24.9 124
460-3-60
STD
414 508 1 5.1 39 1 0.4 0.3
2.2 NO 9.0 15 8.9 46
YES 11.7 15 11.4 48
HS 2.6 NO 9.4 15 9.3 60
YES 12.1 15 11.8 63
575-3-60
STD
518 632 1 4.2 31
10.4
0.3†
1.9 NO 7.6 10 7.5 36
YES 9.7 15 9.5 38
HS 2.0 NO 7.7 10 7.6 43
YES 9.8 15 9.6 44
Perfect Humidity 1 0.4† 2.6† NO 7.7 10 8.0 48
YES 9.8 15 9.6 50
FLA Full Load Amps
HACR — Heating, Air Conditioning and Refrigeration
IFM Indoor (Evaporator) Fan Motor
LRA Locked Rotor Amps
MCA Minimum Circuit Amps
MOCP — Maximum Overcurrent Protection
NEC National Electrical Code
OFM Outdoor (Condenser) Fan Motor
RLA Rated Load Amps
UL Underwriters’ Laboratories
= 100 x max voltage deviation from average voltage
average voltage
Average Voltage = 452 + 464 + 455
3
= 1371
3
= 457
% Voltage Imbalance = 100 x 7
457
= 1.53%
IMPORTANT: If the supply voltage phase imbalance is more than 2%, contact
your local electric utility company immediately.
POWER EXHAUST
PART NO . Application
usage MCA
(230 v) MCA
(460 v) MCA
(575 v)
MOCP
(for
separate
power
source)
CRPWREXH030A01 036-072 1.6 N/A 0.64 15
CRPWREXH021A01 036-072 N/A 0.68 N/A 15
CRPWREXH028A01 ALL* 1.7 N/A 0.68 15
CRPWREXH029A01 ALL N/A 0.7 N/A 15