81
ELECTRICAL DATA (cont)
LEGEND
*Used to determine minimum disconnect per NEC.
†Fuse or HACR circuit breaker.
NOTES:
1. In compliance with NEC requirements for multimotor and combination load equipment (refer
to NEC Articles 430 and 440), the overcurrent protective device for the unit shall be fuse or
HACR breaker. Canadian units may be fuse or circuit breaker.
2. Unbalanced 3-Phase Supply Voltage
Never operate a motor where a phase imbalance in supply voltage is greater than 2%. Use
the following formula to determine the percent of voltage imbalance.
% Voltage Imbalance
Example: Supply voltage is 460-3-60.
AB = 452 v
BC = 464 v
AC = 455 v
= 457
Determine maximum deviation from average voltage.
(AB) 457 – 452 = 5 v
(BC) 464 – 457 = 7 v
(AC) 457 – 455 = 2 v
Maximum deviation is 7 v.
Determine percent of voltage imbalance.
= 1.53%
This amount of phase imbalance is satisfactory as it is below the maximum allowable 2%.
IMPORTANT: If the supply voltage phase imbalance is more than 2%, contact your local
electric utility company immediately.
3. For units with power exhaust: If a single power source is to be used, size wire to include
power exhaust MCA and MOCP. Check MCA and MOCP when power exhaust is powered
through the unit (must be in accordance with NEC and/or local codes). Determine the new
MCA including the power exhaust using the following formula:
MCA New = MCA unit only + MCA of Power Exhaust
For example, using a 580F060 unit with MCA = 28.9 and MOCP = 35, with
CRPWREXH030A01 power exhaust.
MCA New = 28.9 amps + 1.6 amps = 30.5 amps
If the new MCA does not exceed the published MOCP, then MOCP would not change. The
MOCP in this example is 35 amps, the MCA New is below 35, therefore the MOCP is
acceptable. If “MCA New” is larger than the published MOCP, raise the MOCP to the next
larger size. For separate power, the MOCP for the power exhaust will be 15 amps per NEC.
POWER EXHAUST ELECTRICAL DATA
*Single or three phase.
UNIT SIZE
580F NOMINAL
V-PH-Hz IFM
TYPE CONV
OUTLET
VOLTAGE
RANGE COMPRESSOR (each) OFM (each) IFM
FLA
COMBUSTION
FAN MOTOR POWER SUPPLY MINIMUM UNIT
DISCONNECT SIZE*
Min Max Qty RLA LRA Qty FLA FLA MCA MOCP† FLA LRA
103
(81/2 Ton)
208/230-3-60 STD NO
187 254 2 17.3 120.0 2 1.4 5.8 0.6
44.3 50 46 272
YES 49.1 60 52 277
HIGH NO 10.6 49.1 60 52 316
YES 53.9 60 57 320
460-3-60 STD NO
414 508 2 7.9 70.0 2 0.7 2.6 0.3
21.0 25 22 149
YES 23.2 30 24 151
HIGH NO 4.8 23.2 30 24 171
YES 25.4 30 27 173
575-3-60
STD NO
518 632 2 5.5 50.0 2 0.6
2.0
0.3
16.7 20 17 109
YES 18.4 25 19 111
HIGH NO 2.8 18.5 25 19 126
YES 20.2 25 21 128
120
(10 Ton)
208/230-3-60
STD NO
187 254 2 15.8 130 2 1.4
5.8
0.6
44.2 50 46 307
YES 50.2 60 52 311
ALT NO 7.5 45.9 50 48 326
YES 51.9 60 54 330
HIGH NO 15.0 53.4 60 57 374
YES 59.4 70 62 378
460-3-60
STD NO
414 508 2 7.9 64 2 0.7
2.6
0.3
21.8 25 23 152
YES 27.8 30 25 154
ALT NO 3.4 22.6 25 24 191
YES 25.3 30 26 193
HIGH NO 7.4 26.6 30 28 185
YES 29.3 35 31 187
575-3-60
STD NO
518 632 2 6.6 52 2 0.6
2.0
0.3
18.1 25 19 123
YES 24.1 25 21 109
ALT NO 2.0 18.7 25 20 155
YES 24.7 25 22 141
HIGH NO 2.8 21.9 30 23 150
YES 24.6 30 25 136
121
(10 Ton)
208/230-3-60
STD NO
187 254 2 15.8 130 2 1.4
5.8
0.6
44.6 50 46 307
YES 49.4 60 52 312
ALT NO 7.5 46.3 60 48 326
YES 51.1 60 54 331
HIGH NO 15.0 53.8 60 57 374
YES 58.6 70 62 379
460-3-60
STD NO
414 508 2 7.9 64 2 0.7
2.6
0.3
22.0 25 23 152
YES 24.2 30 25 154
ALT NO 3.4 22.8 25 24 191
YES 25.0 30 26 193
HIGH NO 7.4 26.8 30 28 185
YES 29.0 35 30 187
575-3-60
STD NO
518 632 2 6.6 52 2 0.6
2.0
0.3
18.1 20 19 123
YES 19.8 25 21 125
ALT NO 2.8 18.7 20 20 150
YES 20.4 25 22 156
HIGH NO 3.3 21.9 25 23 155
YES 23.6 25 25 151
FLA Full Load Amps
HACR — Heating, Air Conditioning and Refrigeration
IFM Indoor (Evaporator) Fan Motor
LRA Locked Rotor Amps
MCA Minimum Circuit Amps
MOCP — Maximum Overcurrent Protection
NEC National Electrical Code
OFM Outdoor (Condenser) Fan Motor
RLA Rated Load Amps
= 100 x max voltage deviation from average voltage
average voltage
Average Voltage = 452 + 464 + 455
3
= 1371
3
% Voltage Imbalance = 100 x 7
457
POWER EXHAUST
PART NO. APPLICATION
USAGE MCA
(230 V) MCA
(460 V) MCA
(575 V)
MOCP
(separate
power source
only)
CRPWREXH030A01 036-073* 1.6 N/A 0.64 15
CRPWREXH021A01 036-073 N/A 0.68 N/A 15
CRPWREXH022A01 090-151* 3.4 N/A 1.32 15
CRPWREXH023A01 090-151 N/A 1.4 N/A 15
CRPWREXH028A01 ALL* 1.7 N/A 0.68 15
CRPWREXH029A01 ALL N/A 0.7 N/A 15
580F036-151