19
ARI* CAPACITY RATINGS — 581A210-300
LEGEND
*Air Conditioning and Refrigeration Institute.
†IPLV values are calculated based on control configuration T.CTL = 2
(2 Stage Y1).
**Size 300 unit is not listed with ARI, but is tested to ARI standards.
NOTES:
1. Rated in accordance with ARI Standards 360-93 and 270-95.
2. ARI ratings are net values, reflecting the effects of circulating fan heat.
3. Ratings are based on:
Cooling Standard: 80 F db, 67 F wb indoor entering-air temperature and
95 F db air entering outdoor unit.
IPLV Standard: 80 F db, 67 F wb indoor entering-air temperature and 80 F
db outdoor entering-air temperature.
4. All 581A210-300 units are in compliance with ASHRAE 90.1 2001 Energy
Standard for minimum EER requirements. Refer to state and local codes or
visit the following website: http://bcap-energy.org to determine if compliance
with this standard pertains to a given geographical area of the United States.
HEATING CAPACITIES AND EFFICIENCIES — 581A210-300

VERTICAL SUPPLY — NATURAL GAS

NOTE: All units are 2-stage gas heat.

HORIZONTAL SUPPLY — NATURAL GAS

*7000 cfm minimum recommended above 1.0 in. wg external static pressure.
NOTE: All units are 2-stage gas heat.

VERTICAL SUPPLY — PROPANE

NOTE: All units are 2-stage gas heat.

HORIZONTAL SUPPLY — PROPANE

*7000 cfm minimum recommended above 1.0 in. wg external static pressure.
NOTE: All units are 2-stage gas heat.
UNIT
581A NOMINAL
TONS CFM NET COOLING
CAPACITY (Btuh) TOTAL
kW EER SOUND RATING
(dB) IPLV†
210 18 5,500 200,000 18.5 10.8 81.7 12.0
240 20 6,000 234,000 21.7 10.8 81.7 11.9
300** 25 7,500 278,000 27.8 10.0 84.6 10.9
db Dry Bulb
EER — Energy Efficiency Ratio
IPLV — Integrated Part-Load Values
wb Wet Bulb
UNIT
581A HEATING INPUT
(Btuh) Stage 2/Stage 1 OUTPUT CAPACITY
(Btuh) TEMPERATURE
RISE (F) STEADY-STATE
EFFICIENCY % MINIMUM
HEATING CFM
210250 250,000/199,000 205,000 15-45 82% 4218
210365 365,000/281,000 296,000 25-55 81% 4977
210400 400,000/317,000 328,000 25-55 82% 5522
240250 250,000/199,000 205,000 15-45 82% 4218
240365 365,000/281,000 296,000 25-55 81% 4977
240400 400,000/317,000 328,000 25-55 82% 5522
300250 250,000/199,000 205,000 15-45 82% 4218
300365 365,000/281,000 296,000 25-55 81% 4977
300400 400,000/317,000 328,000 25-55 82% 5522
UNIT
581A HEATING INPUT
(Btuh) Stage 2/Stage 1 OUTPUT CAPACITY
(Btuh) TEMPERATURE
RISE (F) STEADY-STATE
EFFICIENCY % MINIMUM
HEATING CFM
210250 250,000/199,000 205,000 15-45 82% 4218
210365 365,000/281,000 296,000 25-55 81% 4977
210400 400,000/317,000 328,000 25-55 82% 5522
240250 250,000/199,000 205,000 15-45 82% 4218
240365 365,000/281,000 296,000 25-55 81% 4977
240400 400,000/317,000 328,000 25-55 82% 5522
300250 250,000/199,000 205,000 15-45 82% 4218
300365 365,000/281,000 296,000 25-55 81% 4977*
300400 400,000/317,000 325,000 25-55 82% 5522*
UNIT
581A HEATING INPUT
(Btuh) Stage 2/Stage 1 OUTPUT CAPACITY
(Btuh) TEMPERATURE
RISE (F) STEADY-STATE
EFFICIENCY % MINIMUM
HEATING CFM
210250 250,000/207,000 205,000 15-45 82% 4218
210365 365,000/291,000 296,000 25-55 81% 4480
210400 400,000/331,000 328,000 25-55 82% 5522
240250 250,000/207,000 205,000 15-45 82% 4218
240365 365,000/291,000 296,000 25-55 81% 4480
240400 400,000/331,000 328,000 25-55 82% 5522
300250 250,000/207,000 205,000 15-45 82% 4218
300365 365,000/291,000 296,000 25-55 81% 4480
300400 400,000/331,000 328,000 25-55 82% 5522
UNIT
581A HEATING INPUT
(Btuh) Stage 2/Stage 1 OUTPUT CAPACITY
(Btuh) TEMPERATURE
RISE (F) STEADY-STATE
EFFICIENCY % MINIMUM
HEATING CFM
210250 225,000/207,000 185,000 15-45 82% 3807
210365 329,000/291,000 266,000 25-55 81% 4480
210400 356,000/331,000 292,000 25-55 82% 4916
240250 225,000/207,000 184,500 15-45 82% 3796
240365 329,000/291,000 266,000 25-55 81% 4480
240400 356,000/331,000 292,000 25-55 82% 4916
300250 225,000/207,000 185,000 15-45 82% 3807
300365 329,000/291,000 266,000 25-55 81% 4480*
300400 356,000/331,000 292,000 25-55 82% 4920*