99
PERFORMANCE DATA (cont)
COOLING CAPACITIES — UNITS WITH PERFECT HUMIDITY™ ADAPTIVE DEHUMIDIFICATION SYSTEM OPTION
LEGEND
NOTES:
1. Direct interpolation is permissible. Do not extrapolate.
2. The following formulas may be used:
Where: hewb = Enthalpy of air entering evaporator coil.
3. The SHC is based on 80 F edb temperature of air entering evapo-
rator coil.
Below 80 F edb, subtract (corr factor x cfm) from SHC.
Above 80 F edb, add (corr factor x cfm) to SHC.
Correction Factor = 1.10 x (1 – BF) x (edb – 80).
581B036 (3 TONS) — SUBCOOLING MODE
Temp (F )
Air Ent
Condenser
(Edb)
Air Entering Evaporator — Cfm/BF
900/0.14 1200/0.17 1500/0.20
Air Entering Evaporator — Ewb (F)
72 67 62 72 67 62 72 67 62
75 TC 41.3 37.3 34.3 43.5 39.2 35.9 45.5 41.6 38.2
SHC 17.5 22.4 26.7 19.6 25.5 31.2 21.5 28.5 35.2
kW 2.19 2.14 2.10 2.21 2.16 2.14 2.24 2.19 2.16
85 TC 38.6 34.4 31.6 41.3 37.5 33.3 43.5 38.6 35.5
SHC 15.2 20.1 25.1 17.1 23.2 29.0 18.9 26.3 32.9
kW 2.46 2.40 2.37 2.47 2.43 2.40 2.51 2.45 2.42
95 TC 35.9 31.4 28.8 39.2 35.9 30.6 41.3 35.7 32.9
SHC 13.0 17.9 23.3 14.5 21.1 26.9 16.1 24.2 30.6
kW 2.74 2.68 2.63 2.76 2.74 2.67 2.80 2.75 2.71
105 TC 33.8 29.7 27.4 36.3 32.2 28.7 38.1 32.8 30.4
SHC 10.9 15.8 21.0 12.5 18.9 24.6 14.0 21.7 28.1
kW 3.05 3.00 2.97 3.09 3.04 2.99 3.12 3.07 3.03
115 TC 31.8 28.0 25.5 33.2 28.7 26.5 34.9 30.0 27.9
SHC 9.0 13.7 18.4 10.3 16.8 22.3 11.9 19.3 25.2
kW 3.40 3.36 3.31 3.45 3.38 3.32 3.48 3.41 3.37
125 TC 28.7 26.3 23.4 29.7 25.5 22.9 31.3 27.1 25.5
SHC 6.9 12.2 17.3 7.9 14.5 20.6 9.2 17.3 22.3
kW 3.78 3.73 3.66 3.84 3.77 3.71 3.87 3.79 3.75
581B036 (3 TONS) — HOT GAS REHEAT MODE
Temp (F )
Air Ent
Condenser
(Edb)
Air Entering Evaporator — Ewb (F)
75 Dry Bulb
62.5 Wet Bulb
(50% Relative)
75 Dry Bulb
64 Wet Bulb
(55% Relative)
75 Dry Bulb
65.3 Wet Bulb
(60% Relative)
Air Entering Evaporator — Cfm
900 1200 1500 900 1200 1500 900 1200 1500
80 TC 12.83 15.84 18.20 13.24 16.31 18.73 13.58 16.72 19.18
SHC 4.06 5.69 6.98 2.21 3.83 5.12 .59 2.20 3.50
kW 2.12 2.12 2.12 2.13 2.13 2.13 2.14 2.14 2.14
75 TC 13.61 16.44 18.67 14.03 16.93 19.20 14.39 17.34 19.67
SHC 4.62 6.16 7.37 2.89 4.43 5.65 1.40 2.93 4.15
kW 2.11 2.11 2.11 2.12 2.12 2.12 2.14 2.14 2.14
70 TC 14.39 17.05 19.14 14.82 17.54 19.68 15.19 17.96 20.15
SHC 5.17 6.62 7.77 3.58 5.03 6.18 2.20 3.65 4.80
kW 2.10 2.10 2.10 2.12 2.12 2.12 2.13 2.13 2.13
60 TC 15.95 18.26 20.08 16.40 18.77 20.63 16.79 19.21 21.11
SHC 6.27 7.55 8.56 4.95 6.23 7.24 3.81 5.09 6.10
kW 2.09 2.09 2.09 2.11 2.11 2.11 2.12 2.12 2.12
50 TC 17.50 19.48 21.02 17.98 20.00 21.58 18.40 20.45 22.07
SHC 7.37 8.47 9.35 6.32 7.43 8.30 5.42 6.52 7.39
kW 2.07 2.07 2.07 2.10 2.10 2.10 2.12 2.12 2.12
40 TC 19.06 20.69 21.07 19.56 21.23 22.54 20.00 21.70 23.03
SHC 8.47 9.40 10.13 7.71 8.63 9.36 7.02 7.95 8.69
kW 2.06 2.06 2.06 2.08 2.08 2.08 2.11 2.11 2.11
BF Bypass Factor
Edb — Entering Dry Bulb
Ewb — Entering Wet Bulb
kW Compressor Motor Power Input
SHC — Sensible Heat Capacity (1000 Btuh) Gross
TC Total Capacity (1000 Btuh) Gross
tldb =t
edb sensible capacity (Btuh)
1.10 x cfm
tlwb = Wet-bulb temperature corresponding to enthalpy of air
leaving evaporator coil (hlwb)
hlwb =h
ewb total capacity (Btuh)
4.5 x cfm
581B036-150