223
ELECTRICAL DATA
LEGEND
*Fuse or HACR circuit breaker.
NOTES:
1. In compliance with NEC requirements for multimotor and combination load
equipment (refer to NEC Articles 430 and 440), the overcurrent protective
device for the unit shall be fuse or HACR breaker. Canadian units may be
fuse or circuit breaker.
2. Unbalanced 3-Phase Supply Voltage
Never operate a motor where a phase imbalance in supply voltage is
greater than 2%. Use the following formula to determine the percent voltage
imbalance.
% Voltage Imbalance
EXAMPLE: Supply voltage is 460-3-60.
Determine maximum deviation from average voltage.
(AB) 457 – 452 = 5 v
(BC) 464 – 457 = 7 v
(AC) 457 – 455 = 2 v
Maximum deviation is 7 v.
Determine percent voltage imbalance.
= 1.53%
This amount of phase imbalance is satisfactory as it is below the maximum
allowable 2%.
IMPORTANT: If the supply voltage phase imbalance is more than 2%, con-
tact your local electric utility company immediately.
UNIT
580F
NOMINAL
VOLTAGE
(3 Ph, 60 Hz)
VOLTAGE
RANGE COMPRESSOR OFM IFM POWER
EXHAUST COMBUSTION
FAN MOTOR POWER
SUPPLY
No. 1 No. 1A No. 2
Min Max RLA LRA RLA LRA RLA LRA Qty Hp FLA (ea) Hp FLA FLA LRA FLA MCA MOCP*
180
208/230 187 253 32.1 195 — — 20.7 156 3 0.5 1.7 5.0 15.8/15.8 — — 0.57 82/82 110/110
4.6 18.8 0.57 86/86 110/110
460 414 508 16.4 95 — — 10 70 3 0.5 0.8 5.0 7.9 — — 0.30 41 50
2.3 6.0 0.30 43 50
575 518 633 12 80 — — 8.2 54 3 0.5 0.75 5.0 6.0 — — 0.57 31 40
2.1 4.8 0.57 34 40
210
208/230 187 253 30.1 225 — — 28.8 195 3 0.5 1.7 5.0 15.8/15.8 — — 0.57 87/87 110/110
4.6 18.8 0.57 92/92 110/110
460 414 508 15.5 114 — — 14.7 95 3 0.5 0.8 5.0 7.9 — — 0.30 44 50
2.3 6.0 0.30 47 60
575 518 632.5 12.1 80 — — 10.7 80 3 0.5 0.75 5.0 6.0 — — 0.57 34 40
2.1 4.8 0.57 36 40
240
208/230 187 253 42 239 — — 33.6 225 2 1 6.6 7.5 25.0/25.0 — — 0.57 124/124 150/150
4.6 18.8 0.57 129/129 150/150
460 414 508 19.2 125 — — 17.3 114 2 1 3.3 7.5 13.0 — — 0.30 61 80
2.3 6.0 0.30 63 80
575 518 633 13.8 80.0 — — 13.5 80.0 2 1.0 3.4 7.5 10.0 — — 0.57 48 60
2.1 4.8 0.57 50 60
300
208/230 187.2 253 20.7 156 20.7 156 47.1 245 6 0.5 1.7 10.0 28.0/28.0 — — 0.57 138/138 175/175
4.6 18.8 0.57 143/143 150/175
460 414 508 10 75 10 75 19.6 125 6 0.5 0.8 10.0 14.6 — — 0.30 64 80
2.3 6 0.30 66 80
575 517.5 632.5 8.2 54 8.2 54 15.8 100 6 0.5 0.8 10.0 13.0 — — 0.57 54 60
2.1 4.8 0.57 56 70
FLA — Full Load Amps
HACR — Heating, Air Conditioning and Refrigeration
IFM — Indoor (Evaporator) Fan Motor
LRA — Locked Rotor Amps
MCA — Minimum Circuit Amps
MOCP — Maximum Overcurrent Protection
NEC — National Electrical Code
OFM — Outdoor (Condenser) Fan Motor
RLA — Rated Load Amps
= 100 x max voltage deviation from average voltage
average voltage
AB = 452 v
BC = 464 v
AC = 455 v
Average Voltage = 452 + 464 + 455
3
=1371
3
= 457
% Voltage Imbalance = 100 x 7
457
580F180-300