580J

Table 24 – EconoMi$er IV Sensor Usage

 

ECONOMI$ER IV WITH OUTDOOR AIR DRY

APPLICATION

BULB SENSOR

 

Accessories Required

Outdoor Air

None. The outdoor air dry bulb sensor is

Dry Bulb

factory installed.

Differential

CRTEMPSN002A00*

Dry Bulb

 

 

 

Single Enthalpy

HH57AC078

Differential

HH57AC078 and CRENTDIF004A00*

Enthalpy

 

 

 

CO2 for DCV

 

 

 

Control using a

33ZCSENCO2

Wall-Mounted

 

 

 

CO2 Sensor

 

 

 

CO2 for DCV

33ZCSENCO2† and

O

 

Control using a

CRCBDIOX005A00††

Duct-Mounted

33ZCASPCO2**

R

CO2 Sensor

 

 

 

*CRENTDIF004A00 and CRTEMPSN002A00 accessories are used on many different base units. As such, these kits may contain parts that will not be needed for installation.

† 33ZCSENCO2 is an accessory CO2 sensor.

**33ZCASPCO2 is an accessory aspirator box required for duct-mounted applications.

††CRCBDIOX005A00 is an accessory that contains both 33ZCSENCO2 and 33ZCASPCO2 accessories.

3.Use the Up/Down button to select the preset number. (See Table 23.)

4.Press Enter to lock in the selection.

5.Press Mode to exit and resume normal operation.

The custom settings of the CO2 sensor can be changed anytime after the sensor is energized. Follow the steps below to change the non-standard settings:

1.Press Clear and Mode buttons. Hold at least 5 seconds until the sensor enters the Edit mode.

2.Press Mode twice. The STDSET Menu will appear.

3.Use the Up/Down button to toggle to the NONSTD menu and press Enter.

4.Use the Up/Down button to toggle through each of the nine variables, starting with Altitude, until the desired setting is reached.

5.Press Mode to move through the variables.

6.Press Enter to lock in the selection, then press Mode to continue to the next variable.

Dehumidification of Fresh Air with DCV (Demand Controlled Ventilation) Control

If normal rooftop heating and cooling operation is not adequate for the outdoor humidity level, an energy recovery unit and/or a dehumidification option should be considered.

EconoMi$er IV Preparation

This procedure is used to prepare the EconoMi$er IV for troubleshooting. No troubleshooting or testing is done by performing the following procedure.

NOTE: This procedure requires a 9-v battery, 1.2 kilo-ohm resistor, and a 5.6 kilo-ohm resistor which are not supplied with the EconoMi$er IV.

IMPORTANT: Be sure to record the positions of all potentiometers before starting troubleshooting.

1.Disconnect power at TR and TR1. All LEDs should be off. Exhaust fan contacts should be open.

2.Disconnect device at P and P1.

3.Jumper P to P1.

4.Disconnect wires at T and T1. Place 5.6 kilo-ohm resistor across T and T1.

5.Jumper TR to 1.

6.Jumper TR to N.

7.If connected, remove sensor from terminals SO and +. Connect 1.2 kilo-ohm 4074EJM checkout resistor across terminals SO and +.

8.Put 620-ohm resistor across terminals SR and +.

9.Set minimum position, DCV setpoint, and exhaust potentiometers fully CCW (counterclockwise).

10.Set DCV maximum position potentiometer fully CW (clockwise).

11.Set enthalpy potentiometer to D.

12.Apply power (24 vac) to terminals TR and TR1.

Differential Enthalpy

To check differential enthalpy:

1.Make sure EconoMi$er IV preparation procedure has been performed.

2.Place 620-ohm resistor across SO and +.

3.Place 1.2 kilo-ohm resistor across SR and +. The Free Cool LED should be lit.

4.Remove 620-ohm resistor across SO and +. The Free Cool LED should turn off.

5.Return EconoMi$er IV settings and wiring to normal after completing troubleshooting.

Single Enthalpy

To check single enthalpy:

1.Make sure EconoMi$er IV preparation procedure has been performed.

2.Set the enthalpy potentiometer to A (fully CCW). The Free Cool LED should be lit.

3.Set the enthalpy potentiometer to D (fully CW). The Free Cool LED should turn off.

4.Return EconoMi$er IV settings and wiring to normal after completing troubleshooting.

DCV (Demand Controlled Ventilation) and Power Exhaust

To check DCV and Power Exhaust:

1.Make sure EconoMi$er IV preparation procedure has been performed.

2.Ensure terminals AQ and AQ1 are open. The LED for both DCV and Exhaust should be off. The actuator should be fully closed.

3.Connect a 9-v battery to AQ (positive node) and AQ1 (negative node). The LED for both DCV and Exhaust should turn on. The actuator should drive to between 90 and 95% open.

4.Turn the Exhaust potentiometer CW until the Exhaust LED turns off. The LED should turn off when the potentiometer is approximately 90%. The actuator should remain in position.

58

Page 58
Image 58
Bryant F, 580J*08--14D EconoMi$er IV Sensor Usage, EconoMi$er IV Preparation, Differential Enthalpy, Single Enthalpy

580J*08--14D, F specifications

The Bryant F,580J*08--14D is an advanced heating and cooling system engineered for optimal performance and energy efficiency in residential and commercial applications. This innovative unit is designed to provide exceptional climate control while reducing operational costs, making it an ideal choice for those seeking reliable HVAC solutions.

One of the standout features of the Bryant F,580J*08--14D is its versatile heating and cooling capabilities. This system employs a two-stage compressor, which allows for precise temperature regulation and improved energy efficiency. This dual-stage operation ensures that the system can adapt to varying environmental conditions, providing enhanced comfort without excessive energy use.

The system is equipped with advanced inverter technology, which enables smoother operation and quieter performance. This technology adjusts the compressor speed based on the heating or cooling demand, leading to increased efficiency and reduced energy consumption. Additionally, the inverter system contributes to less noise during operation, creating a serene indoor environment.

The Bryant F,580J*08--14D also features a user-friendly thermostat that allows for easy temperature adjustments and scheduling. This smart thermostat is compatible with mobile devices, enabling users to monitor and control their HVAC system remotely. This feature provides added convenience and ensures that the system is operating efficiently, even when homeowners are away.

Energy efficiency is a hallmark of the Bryant F,580J*08--14D. The system meets and often exceeds ENERGY STARĀ® standards, making it one of the more eco-friendly options available in the market today. By utilizing energy-saving technologies and innovative designs, the system helps to lower utility bills and reduce the environmental impact.

Durability and reliability are key characteristics of the Bryant F,580J*08--14D. Constructed with high-quality materials and components, this unit is designed to withstand the rigors of changing weather conditions while maintaining consistent performance. Additionally, it comes equipped with a robust warranty, providing peace of mind for users investing in this heating and cooling solution.

In summary, the Bryant F,580J*08--14D is a top-tier HVAC system that boasts advanced technologies, exceptional energy efficiency, and user-friendly features. Its combination of reliable performance and modern conveniences makes it a standout choice for anyone looking to enhance their home's or business's climate control system, providing comfort and savings for years to come.