580J
Input 5
This input is a discrete input and can be configured to be one of five different inputs: No Function, Fire Shutdown, Fan Status, Filter Status, or Remote Occupancy. This input can also be configured to be either Normally Open (N/O) or Normally Closed (N/C). Input 5 is factory wired to pin
Factory Default = Fire Shutdown and N/C
NOTE: Fire Shutdown input comes from
Input 8
This input is a discrete input and can be configured to be one of five different inputs: No Function, Enthalpy Switch, Fan Status, Filter Status, or Remote Occupancy. This input can also be configured to be either Normally Open (N/O) or Normally Closed (N/C). Input 8 is factory wired to pin
Factory Default = No Function and N/O
Input 9
This input is a discrete input and can be configured to be one of five different inputs: No Function, Humidistat, Fan Status, Filter Status, or Remote Occupancy. This input can also be configured to be either Normally Open (N/O) or Normally Closed (N/C). Input 9 is factory and field wired to pin
Factory Default = Humidistat and N/O
Space Sensor Type
This tells the controller what type of space sensor is installed to run the unit. The three types that can be used are the T55 space sensor, the T56 space sensor, or the RS space sensor.
Factory Default = T55 Type
Input 1 Function
This input is an analog input and can be configured to be one of five different inputs: No Sensor, IAQ Sensor, OAQ Sensor, Space RH Sensor, or Outdoor RH Sensor. Input 1 is wired to pin
Factory Default = No Sensor
Input 2 Function
This input is an analog input and can be configured to be one of five different inputs: No Sensor, IAQ Sensor, OAQ Sensor, Space RH Sensor, or Outdoor RH Sensor. Input 2 is wired to pin
Factory Default = No Sensor
Setpoint Slider Range
This sets the slider range of the space sensor (with this built in function). The slider is used to offset the current control setpoint.
Factory Default = 5 n_F Range =
T55/56 Override Duration
This sets the occupancy override duration when the override button is pushed on the space sensor.
Factory Default = 1 hr Range =
IAQ Low Reference @ 4mA
This is used when an IAQ sensor is installed on Input 1 or
2.This value is displayed and used when 4mA is seen at the input.
Factory Default = 0 PPM
Range =
IAQ High Reference @ 20mA
This is used when an IAQ sensor is installed on Input 1 or
2.This value is displayed and used when 20mA is seen at the input.
Factory Default = 2000 PPM Range =
NOTE: IAQ low Reference @ 4mA and IAQ High Reference @ 20mA are used to set the linear curve of mA vs. PPM.
OAQ Low Reference @ 4mA
This is used when an OAQ sensor is installed on Input 1 or 2. This value is displayed and used when 4mA is seen at the input.
Factory Default = 0 PPM Range =
OAQ High Reference @ 20mA
This is used when an OAQ sensor is installed on Input 1 or 2. This value is displayed and used when 20mA is seen at the input.
Factory Default = 2000 PPM Range =
NOTE: OAQ low Reference @ 4mA and OAQ High Reference @ 20mA are used to set the linear curve of mA vs. PPM.
Economizer
Economizer Exists
This point tells the controller if there is an economizer installed on the unit.
Factory Default = NO if no economizer YES if there is an economizer installed
Economizer Minimum Position
This defines the lowest economizer position when the indoor fan is running and the building is occupied.
Factory Default = 20% Range =
Economizer High OAT Lockout
If the outdoor air temperature rises above this value, economizer cooling will be disabled and dampers will return and stay at minimum position.
Factory Default = 75_F Range =
66