Bryant 580J*08--14D, F appendix Burner Ignition, Spark Adjustment, LED Error Code Description

Models: F

1 85
Download 85 pages 43.69 Kb
Page 29
Image 29
Fig. 38 - Spark Adjustment (08-14)

125,000/90,000 BTUH INPUT

180,000/120,000 BTUH INPUT

240,000/180,000 BTUH INPUT 250,000/200,000 BTUH INPUT

C08447

Fig. 38 - Spark Adjustment (08-14)

580J

Burner Ignition

Unit is equipped with a direct spark ignition 100% lockout system. Integrated Gas Unit Controller (IGC) is located in the control box. (See Fig. 37.) The IGC contains a self-diagnostic LED (light-emitting diode). A single LED on the IGC provides a visual display of operational or sequential problems when the power supply is uninterrupted. (See Fig. 40.) When a break in power occurs, the IGC will be reset (resulting in a loss of fault history) and the indoor (evaporator) fan ON/OFF times will be reset. The LED error code can be observed through the viewport. During servicing refer to the label on the control box cover or Table 9 for an explanation of LED error code descriptions.

If lockout occurs, unit may be reset by interrupting power supply to unit for at least 5 seconds.

Table 9 – LED Error Code Description*

LED INDICATION

ERROR CODE

DESCRIPTION

 

 

 

ON

Normal Operation

 

 

OFF

Hardware Failure

 

 

2 Flashes

Limit Switch Fault

 

 

3 Flashes

Flame Sense Fault

 

 

4 Flashes

4 Consecutive Limit Switch Faults

 

 

5 Flashes

Ignition Lockout Fault

 

 

6 Flashes

Induced--- Draft Motor Fault

 

 

7 Flashes

Rollout Switch Fault

 

 

8 Flashes

Internal Control Fault

 

 

9 Flashes

Software Lockout

 

 

LEGEND

LED --- Light Emitting Diode

*A 3 – second pause exists between LED error code flashes. If more than one error code exists, all applicable codes will be displayed in numerical sequence.

IMPORTANT: Refer to Troubleshooting Table 13 and 14 for additional information.

29

Page 29
Image 29
Bryant 580J*08--14D, F appendix Burner Ignition, Spark Adjustment, LED Error Code Description