Bryant F, 580J*08--14D appendix Module Status Report Modstat Example

Models: 580J*08--14D F

1 85
Download 85 pages 43.69 Kb
Page 48
Image 48

580J

Device

Instance: 0160001

 

1 PRGs

loaded.

1 PRGs running.

 

Module status:

 

 

Firmware sections validated in flash memory

============================================

Boot16-H

- v2.06:001

Jun 19 2007

RTU-MP DRIVER

- v2.09:050

Jun 26 2007

Reset counters:

 

 

11

Power failures

 

0

Brownouts

 

 

18

Commanded warm boots

 

22

Commanded cold boots

 

0

System errors

 

0

Watchdog timeouts

 

System

error message history:

Type Specific

Warning message history:

 

Information message history:

06/29/07 10:49:40

POWERUP: BACnet reinitialize warmstart

Menu file not found.

06/29/07 10:48:35

ARC156 reconfigurations during the last hour (cleared upon reset):

Total

0

Initiated by this node

0

Core board hardware:

Type=147, board=34, manufactured on 05/14/2007, S/N 21A740188N

RAM: 1024 kBytes; FLASH: 1024 kBytes, type = 3

Base board hardware:

Type=147, board=71, manufactured on 05/14/2007, S/N RMP750037N

Largest free heap space = 65536.

Database size = 742082 , used = 352162, free = 389920.

Raw physical switches: 0x01280000

Module Communications:

Network Protocol=BACnet MSTP Master

Network Baud Rate=9600 bps

C07195

Fig. 59 - Module Status Report (Modstat) Example

10.In certain situations, it may be necessary to tweak the MS/TP Protocol timing settings through the BACview6. There are two settings that may be tweaked:

S Max Masters: Defines the highest MS/TP Master MAC address on this MS/TP network. For example, if there are 3 master nodes on an MS/TP network, and their MAC addresses are 1, 8, and 16, then Max Masters would be set to 16 (since this is the highest MS/TP MAC address on the network). This property optimizes MS/TP network communications by preventing token passes and “poll for master” requests to non-existent Master nodes (i.e., in the above example, MAC address 16 would know to pass the token back to MAC address 1 instead of counting up to MAC address 127).

Each MS/TP master node on the network must have their Max Masters set to this same value. The default is

127.

SMaxInfo Frames: This property defines the maximum number of responses that will be sent when our controller gets the token. A valid number is any positive integer. The default is 10 and should be ideal for the majority of applications. In cases where the controller is the target of many requests, this number could be increased as high as 100 or 200.

NOTE: MS/TP networks can be comprised of both Master and Slave nodes. Valid MAC addresses for Master nodes are 0 - 127 and valid addresses for Slave nodes are 0 - 254.

NOTE: See RTU-MP 3rd Party Integration Guide (or alternatively RTU-MP Controls, Start-Up, Operation, and Troubleshooting Instructions (Form 48-50H-T-2T) Appendix) for Protocol Maps.

48

Page 48
Image 48
Bryant F, 580J*08--14D appendix Module Status Report Modstat Example

580J*08--14D, F specifications

The Bryant F,580J*08--14D is an advanced heating and cooling system engineered for optimal performance and energy efficiency in residential and commercial applications. This innovative unit is designed to provide exceptional climate control while reducing operational costs, making it an ideal choice for those seeking reliable HVAC solutions.

One of the standout features of the Bryant F,580J*08--14D is its versatile heating and cooling capabilities. This system employs a two-stage compressor, which allows for precise temperature regulation and improved energy efficiency. This dual-stage operation ensures that the system can adapt to varying environmental conditions, providing enhanced comfort without excessive energy use.

The system is equipped with advanced inverter technology, which enables smoother operation and quieter performance. This technology adjusts the compressor speed based on the heating or cooling demand, leading to increased efficiency and reduced energy consumption. Additionally, the inverter system contributes to less noise during operation, creating a serene indoor environment.

The Bryant F,580J*08--14D also features a user-friendly thermostat that allows for easy temperature adjustments and scheduling. This smart thermostat is compatible with mobile devices, enabling users to monitor and control their HVAC system remotely. This feature provides added convenience and ensures that the system is operating efficiently, even when homeowners are away.

Energy efficiency is a hallmark of the Bryant F,580J*08--14D. The system meets and often exceeds ENERGY STARĀ® standards, making it one of the more eco-friendly options available in the market today. By utilizing energy-saving technologies and innovative designs, the system helps to lower utility bills and reduce the environmental impact.

Durability and reliability are key characteristics of the Bryant F,580J*08--14D. Constructed with high-quality materials and components, this unit is designed to withstand the rigors of changing weather conditions while maintaining consistent performance. Additionally, it comes equipped with a robust warranty, providing peace of mind for users investing in this heating and cooling solution.

In summary, the Bryant F,580J*08--14D is a top-tier HVAC system that boasts advanced technologies, exceptional energy efficiency, and user-friendly features. Its combination of reliable performance and modern conveniences makes it a standout choice for anyone looking to enhance their home's or business's climate control system, providing comfort and savings for years to come.