APPENDIX III. FAN PERFORMANCE (cont.)

APPENDIX III. FAN PERFORMANCE (cont.)

Pulley Adjustment

UNIT

MOTOR/DRIVE

 

 

 

MOTOR PULLEY TURNS OPEN

 

 

 

COMBO

0.0

0.5

1.0

1.5

2.0

2.5

3.0

3.5

4.0

4.5

5.0

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

phase

Standard Static

747

721

695

670

644

618

592

566

541

515

489

08

Medium Static

949

927

906

884

863

841

819

798

776

755

733

 

 

 

3

High Static

1102

1083

1063

1044

1025

1006

986

967

948

928

909

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

phase

Standard Static

838

813

789

764

739

715

690

665

640

616

591

12

Medium Static

1084

1059

1035

1010

986

961

936

912

887

863

838

 

 

 

3

High Static

1240

1218

1196

1175

1153

1131

1109

1087

1066

1044

1022

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

phase

Standard Static

838

813

789

764

739

715

690

665

640

616

591

14

Medium Static

1084

1059

1035

1010

986

961

936

912

887

863

838

 

 

 

3

High Static

1240

1218

1196

1175

1153

1131

1109

1087

1066

1044

1022

 

 

 

 

 

 

 

 

 

 

 

 

 

 

NOTE: Do not adjust pulley further than 5 turns open.