![DC Power Supply Requirement for Each Supply](/images/new-backgrounds/114000/11400063x1.webp)
Chapter 3: 6C105 Setup
ON/OFF |
DC Input Power Strip
2016_99
Figure
ONLY QUALIFIED PERSONNEL SHOULD PERFORM THESE INSTALLATION PROCEDURES.
TO REDUCE THE RISK OF ELECTRIC SHOCK OR ENERGY HAZARDS:
•CONNECT TO A RELIABLY GROUNDED 48/60 VDC SELV SOURCE.
•ENSURE THE BRANCH CIRCUIT OVERCURRENT PROTECTION IS RATED AT A MINIMUM
OF 25 A.
•USE 10 AWG SOLID COPPER CONDUCTORS ONLY.
•ENSURE THAT A READILY ACCESSIBLE DISCONNECT DEVICE THAT IS SUITABLY APPROVED AND RATED, IS INCORPORATED IN THE FIELD WIRING.
TO BE INSTALLED IN A RESTRICTED ACCESS AREA IN ACCORDANCE WITH THE NEC OR THE AUTHORITY HAVING JURISDICTION.
DC Power Supply Requirement for Each Supply
Each DC power supply input requires either a 48 VDC or 60 VDC power source, rated at a minimum of 17 Amps.
| 6C105 Overview and Setup Guide |