Cabletron Systems setup guide 6C105 Setup, DC Power Supply Requirement for Each Supply, 3-12

Models: 6C105

1 38
Download 38 pages 14.91 Kb
Page 32
Image 32
DC Power Supply Requirement for Each Supply

Chapter 3: 6C105 Setup

ON/OFF

DC Input Power Strip

2016_99

Figure 3-6 Power Supply DC ON/OFF Switch and DC Input Power Strip

ONLY QUALIFIED PERSONNEL SHOULD PERFORM THESE INSTALLATION PROCEDURES.

TO REDUCE THE RISK OF ELECTRIC SHOCK OR ENERGY HAZARDS:

CONNECT TO A RELIABLY GROUNDED 48/60 VDC SELV SOURCE.

ENSURE THE BRANCH CIRCUIT OVERCURRENT PROTECTION IS RATED AT A MINIMUM

OF 25 A.

USE 10 AWG SOLID COPPER CONDUCTORS ONLY.

ENSURE THAT A READILY ACCESSIBLE DISCONNECT DEVICE THAT IS SUITABLY APPROVED AND RATED, IS INCORPORATED IN THE FIELD WIRING.

TO BE INSTALLED IN A RESTRICTED ACCESS AREA IN ACCORDANCE WITH THE NEC OR THE AUTHORITY HAVING JURISDICTION.

DC Power Supply Requirement for Each Supply

Each DC power supply input requires either a 48 VDC or 60 VDC power source, rated at a minimum of 17 Amps.

3-12

6C105 Overview and Setup Guide

Page 32
Image 32
Cabletron Systems 6C105 Setup, DC Power Supply Requirement for Each Supply, 3-12, 6C105 Overview and Setup Guide