Section 6. Maintenance and Troubleshooting

6.1.3 Desiccant

Enclosure humidity is monitored in the ET Enclosure and MetData1 systems by an RH chip incorporated into the connector board. Change the desiccant packs when the enclosure RH exceeds 35%. The RH chip should be changed every 3 to 5 years.

In standard weather stations, a humidity indicator card is provided with the enclosure. A small RH sensor (10162) can be purchased separately to record the RH inside the enclosure. Change the desiccant when either the card or the sensor read about 35% RH.

Desiccant may be ordered through Campbell Scientific (DSC 20/4).

Desiccant packs inside of the dataloggers do not require replacement under normal conditions.

6.1.4 Sensor Maintenance

Sensor maintenance should be performed at regular intervals, depending on the desired accuracy and the conditions of use. A suggested maintenance schedule is outlined below.

1 week

Check the pyranometer for level and contamination. Gently clean, if needed.

Visually inspect the wind sensors and radiation shield.

1 month

Check the rain gage funnel for debris and level.

Do a visual/audio inspection of the anemometer at low wind speeds.

Check the filter of the temperature/humidity sensor for contamination.

General Maintenance

An occasional cleaning of the glass on the solar panel will improve its efficiency.

Check sensor leads and cables for cracking, deterioration, proper routing, and strain relief.

Check the tripod or tower for structural damage, proper alignment, and for level/plumb.

6 months

Clean the temperature/humidity sensor.

Clean the Gill Radiation Shield.