Table 4 — Electrical Data, Standard Motors

 

 

VOLTAGE

 

FAN MOTOR

 

POWER SUPPLY

UNIT

V*-PH-Hz

LIMITS

Hp (kW)

 

FLA

Minimum

MOCP

 

 

 

Circuit Amps

 

 

 

 

 

 

 

 

 

208/230-1-60

187-253

1.3

(0.97)

 

7.6

9.5

15

 

208/230-3-60

187-253

2.4

(1.79)

 

5.8

7.3

15

40RM

460-3-60

414-506

2.4

(1.79)

 

2.6

3.3

15

007

575-3-60

518-632

1.0

(0.75)

 

1.4

1.7

15

 

230-3-50

207-253

2.4

(1.79)

 

5.2

6.5

15

 

400-3-50

360-440

2.4

(1.79)

 

2.6

3.3

15

 

208/230-1-60

187-253

2.4

(1.79)

 

11.0

13.8

20

40RM

208/230-3-60

187-253

2.4

(1.79)

 

5.8

7.3

15

460-3-60

414-506

2.4

(1.79)

 

2.6

3.3

15

40RMQ

 

40RMS

575-3-60

518-632

2.0

(1.49)

 

2.4

8.0

15

008

 

 

 

 

 

 

 

 

230-3-50

207-253

2.4

(1.79)

 

5.2

6.5

15

 

 

 

400-3-50

360-440

2.4

(1.79)

 

2.6

3.3

15

 

208/230-1-60

187-253

2.4

(1.79)

 

11.0

13.8

20

 

208/230-3-60

187-253

2.4

(1.79)

 

5.2

6.5

15

40RMS

460-3-60

414-506

2.4

(1.79)

 

2.6

3.3

15

010

575-3-60

518-632

2.0

(1.49)

 

2.3

2.9

15

 

230-3-50

207-253

2.4

(1.79)

 

5.2

6.5

15

 

400-3-50

360-440

2.4

(1.79)

 

2.6

3.3

15

 

208/230-3-60

187-253

2.4

(1.79)

 

5.8

7.5

15

40RM

460-3-60

414-506

2.4

(1.79)

 

2.6

3.3

15

40RMQ

 

 

 

 

 

 

 

 

575-3-60

518-632

2.0

(1.49)

 

2.4

3.0

15

40RMS

 

012

230-3-50

207-253

2.9

(2.16)

 

7.5

9.4

15

 

400-3-50

360-440

2.9

(2.16)

 

3.4

4.3

15

 

208/230-3-60

187-253

2.9

(2.16)

 

7.5

9.4

15

40RM

460-3-60

414-506

2.9

(2.16)

 

3.4

4.3

15

40RMS

575-3-60

518-632

3.0

(2.24)

 

3.8

4.8

15

014

 

 

 

 

 

 

 

 

230-3-50

207-253

2.9

(2.16)

 

7.5

9.4

15

 

 

 

400-3-50

360-440

2.9

(2.16)

 

3.4

4.3

15

 

208/230-3-60

187-253

3.7

(2.76)

 

10.6

13.3

20

40RM

460-3-60

414-506

3.7

(2.76)

 

4.8

6.0

15

40RMQ

 

 

 

 

 

 

 

 

575-3-60

518-632

3.0

(2.24)

 

3.8

4.8

15

40RMS

 

016

230-3-50

207-253

2.9

(2.16)

 

7.5

9.4

15

 

400-3-50

360-440

2.9

(2.16)

 

3.4

4.3

15

 

208/230-3-60

187-253

5.0

(3.73)

 

14.6/12.8

18.3/16.0

30/25

40RM

460-3-60

414-506

5.0

(3.73)

 

6.4

8.0

15

40RMQ

 

 

 

 

 

 

 

 

575-3-60

518-632

5.0

(3.73)

 

5.1

6.4

15

40RMS

 

230-3-50

207-253

5.0

(3.73)

 

15.2

19.0

30

024

 

 

400-3-50

360-440

5.0

(3.73)

 

7.6

9.5

15

 

208/230-3-60

187-253

7.5

(5.59)

 

21.4/19.4

26.9/24.3

45/40

40RM

460-3-60

414-506

7.5

(5.59)

 

9.7

12.1

20

40RMQ

 

 

 

 

 

 

 

 

575-3-60

518-632

7.5

(5.59)

 

7.8

9.8

15

40RMS

 

028

230-3-50

207-253

7.5

(5.59)

 

22.8

28.5

50

 

400-3-50

360-440

7.5

(5.59)

 

11.4

14.3

25

 

208/230-3-60

187-253

10.0

(7.46)

 

28.2/26.8

35.3/33.5

60/60

40RM

460-3-60

414-506

10.0

(7.46)

 

13.4

16.8

30

40RMS

575-3-60

518-632

10.0

(7.46)

 

10.3

12.9

20

034

 

 

 

 

 

 

 

 

230-3-50

207-253

10.0

(7.46)

 

32.2

40.3

70

 

 

 

400-3-50

360-440

10.0

(7.46)

 

16.1

20.1

30

See Legend and Notes on page 23.

22

Page 22
Image 22
Carrier 40RM007-034, 40RMQ008-028, 40RMS008-034 specifications Electrical Data, Standard Motors, Mocp