Table 9E — Medium-Static Drive Data, 60 Hz — SI

 

 

40RM

 

40RM

40RM

40RM

40RM

40RM

40RM

 

40RM

40RMQ

40RMS

40RMQ

40RMQ

40RMQ

40RMQ

UNIT

40RMS

40RMS

007

40RMS

010

40RMS

40RMS

40RMS

40RMS

 

014

034

 

 

008

 

012

016

024

028

 

 

 

 

 

MOTOR DRIVE

 

 

 

 

 

 

 

 

 

Motor Pulley Pitch Diameter (mm)

86.4-

86.4-

86.4-

86.4-

86.4-

94.0-

109.2-

109.2-

109.2-

 

111.8

111.8

111.8

111.8

111.8

119.4

134.6

134.6

134.6

Pulley Factory Setting

2.5

2.5

2.5

2.5

2.5

3.0

3.0

3.0

3.0

Full Turns Open

 

 

 

 

 

 

 

 

 

FAN DRIVE

 

 

 

 

 

 

 

 

 

Pulley Pitch Dia (mm)

224

203

203

203

208

218

239

239

239

Pulley Bore (mm)

25.4

25.4

25.4

25.4

36.5

36.5

36.5

49.2

49.2

Belt No. — Section

1—A

1—A

1—A

1—A

1—A

1—B

1—B

2—B*

2—B*

Belt Pitch (mm)

1074

1024

1024

1024

1049

1062

1062

(2) 986

(2) 986

 

(2) 1011

(2) 1011

 

 

 

 

 

 

 

 

FAN SPEEDS (r/s)

 

 

 

 

 

 

 

 

 

Factory Setting

12.7

14.0

14.0

14.0

13.7

14.0

14.7

14.7

14.7

Range

11.1-14.4

12.2-15.8

12.2-15.8

12.2-15.8

11.9-15.4

12.4-15.7

13.3-16.4

13.3-16.4

13.3-16.4

Max Allowable Speed (r/s)

20.0

20.0

20.0

20.0

20.0

20.0

20.0

18.3

18.3

Change per 1/ Turn of

 

 

 

 

 

 

 

 

 

2

0.328

0.360

0.360

0.360

0.352

0.278

0.255

0.255

0.255

Moveable Motor Pulley

Flange

 

 

 

 

 

 

 

 

 

MAX FULL TURNS FROM

5

5

5

5

5

6

6

6

6

CLOSED POSITION

 

 

 

 

 

 

 

 

 

SHAFTS CENTER DISTANCE (mm)

265-313

265-313

265-313

265-313

265-313

265-313

232-279

169-240

169-240

*Four belts shipped with unit. Use correct set of 2 belts sized according to the pulley setting.

Table 9F — High-Static Drive Data, 60 Hz — SI

 

 

40RM

 

40RM

40RM

40RM

40RM

40RM

40RM

UNIT

40RM

40RMQ

40RMS

40RMQ

40RMQ

40RMQ

40RMQ

40RMS

40RMS

007

40RMS

010

40RMS

40RMS

40RMS

40RMS

 

014

034

 

 

008

 

012

016

024

028

 

 

 

 

 

MOTOR DRIVE

 

 

 

 

 

 

 

 

 

Motor Pulley Pitch Diameter (mm)

86.4-

86.4-

86.4-

86.4-

94.0-

109.2-

109.2-

109.2

109.2-

 

111.8

111.8

111.8

111.8

119.4

134.6

134.6

134.6

134.6

Pulley Factory Setting

2.5

2.5

2.5

2.5

3.0

3.0

3.0

3.0

3.0

Full Turns Open

 

 

 

 

 

 

 

 

 

FAN DRIVE

 

 

 

 

 

 

 

 

 

Pulley Pitch Dia (mm)

178

152*

152

152

188

201

188

203

203

Pulley Bore (mm)

25.4

25.4

25.4

25.4

36.5

36.5

36.5

49.2

49.2

Belt No. — Section

1—A

1—A

1—A

1—A

1—B

1—B

2—B

2—B

2—B

Belt Pitch (mm)

1049

947

947

947

1011

1011

935

935

960

FAN SPEEDS (r/s)

 

 

 

 

 

 

 

 

 

Factory Setting

16.0

18.7

18.7

18.7

16.3

17.7

18.6

17.1

17.1

Range

14.0-

16.3-

16.3-

16.3-

14.4-

15.8-

16.9-

14.6-

14.6-

 

18.1

20.0*†

20.0†

20.0†

18.3

19.5

20.0†

17.9

17.9

Max Allowable Speed (r/s)

20.0

20.0

20.0

20.0

20.0

20.0

20.0

18.3

18.3

Change per 1/ Turn of

 

 

 

 

 

 

 

 

 

2

0.410

0.478

0.478

0.478

0.323

0.307

0.323

0.278

0.278

Moveable Motor Pulley

Flange

 

 

 

 

 

 

 

 

 

MAX FULL TURNS FROM

5

5

5

5

6

6

6

6

6

CLOSED POSITION

 

 

 

 

 

 

 

 

 

SHAFTS CENTER DISTANCE (mm)

265-313

265-313

265-313

265-313

265-313**

232-279

207-255

169-240

169-240

*Values for 3-phase motor shown. For single-phase motor, pulley pitch diameter is 178 mm and resulting fan speed is 14.0-18.3 r/s.

†It is possible to adjust drive so that fan speed exceeds maximum allowable. DO NOT exceed 20 r/s.

**575-v unit has a center distance of 233-279.

33

Page 33
Image 33
Carrier 40RMQ008-028 Medium-Static Drive Data, 60 Hz SI, High-Static Drive Data, 60 Hz SI, 008 012 016 024 028