(SPLIT SYSTEMS WITH 40RM,RMQ,RMS UNITS)
I. PRELIMINARY INFORMATION
OUTDOOR: MODEL NO. _________________________ | INDOOR: MODEL NO. ___________________________ |
SERIAL NO. ___________________________________ | SERIAL NO. ___________________________________ |
ADDITIONAL ACCESSORIES ______________________________________________________________________________
II. PRE-START-UP
OUTDOOR UNIT
IS THERE ANY SHIPPING DAMAGE? _______________ (Y/N) ____
IF SO, WHERE: _________________________________________________________________________________________
_______________________________________________________________________________________________________
WILL THIS DAMAGE PREVENT UNIT | (Y/N) _____ |
|
CHECK POWER SUPPLY. DOES IT AGREE WITH UNIT? | (Y/N) | _____ |
HAS THE GROUND WIRE BEEN CONNECTED? | (Y/N) | _____ |
HAS THE CIRCUIT PROTECTION BEEN SIZED AND INSTALLED PROPERLY? | (Y/N) _______ |
| ||||||
ARE THE POWER WIRES TO THE UNIT SIZED AND INSTALLED PROPERLY? | (Y/N) _______ |
| ||||||
HAVE COMPRESSOR HOLDDOWN BOLTS BEEN LOOSENED? | (Y/N) _____ |
|
| |||||
CONTROLS |
|
|
|
|
|
|
|
|
ARE THERMOSTAT(S) AND INDOOR FAN CONTROL WIRING |
|
|
|
|
| |||
CONNECTIONS MADE AND CHECKED? |
| (Y/N) _____ |
|
|
|
|
| |
ARE ALL WIRING TERMINALS (including main power supply) TIGHT? | (Y/N) _____ |
|
|
| ||||
HAVE OUTDOOR UNIT CRANKCASE HEATERS BEEN ENERGIZED FOR 24 HOURS? | (Y/N) ______ | |||||||
INDOOR UNIT |
|
|
|
|
|
|
|
|
HAS WATER BEEN PLACED IN DRAIN PAN TO CONFIRM PROPER DRAINAGE? |
| (Y/N) | _____ |
| ||||
ARE PROPER AIR FILTERS IN PLACE? |
| (Y/N) ______ |
|
|
|
|
| |
HAVE FAN AND MOTOR PULLEYS BEEN CHECKED FOR PROPER ALIGNMENT? |
| (Y/N) | ______ | |||||
DO THE FAN BELTS HAVE PROPER TENSION? | (Y/N) ______ |
|
|
|
|
| ||
PIPING |
|
|
|
|
|
|
|
|
40RM,RMQ |
|
|
|
|
|
|
|
|
HAS FOAM SHIPPING BLOCK BEEN REMOVED FROM THE TXV (Thermostatic Expansion Valve)? | (Y/N) ______ | |||||||
ARE LIQUID LINE SOLENOID VALVES LOCATED AT THE INDOOR UNIT (40RM) OR OUTDOOR UNIT (40RMQ) | ||||||||
COILS AS REQUIRED? (Y/N) | _________________________________________________________________ | |||||||
HAVE LEAK CHECKS BEEN MADE AT COMPRESSORS, CONDENSERS, INDOOR COILS, |
|
| ||||||
TXVs (Thermostatic Expansion Valves) SOLENOID VALVES, FILTER DRIERS, AND FUSIBLE PLUGS |
| |||||||
WITH A LEAK DETECTOR? | (Y/N) _____ |
|
|
|
|
|
| |
LOCATE, REPAIR, AND REPORT ANY LEAKS. | _______________________________________________________________ | |||||||
HAVE ALL COMPRESSOR SERVICE VALVES BEEN FULLY OPENED (BACKSEATED) | (Y/N) _____ |
| ||||||
ARE THE COMPRESSOR OIL SIGHT GLASSES SHOWING CORRECT LEVELS? | (Y/N) _____ |
| ||||||
40RMS |
|
|
|
|
|
|
|
|
HAS AIR BEEN BLED FROM SYSTEM? | (Y/N) _____ |
|
|
|
|
| ||
HAVE LEAK CHECKS BEEN MADE AT COMPRESSORS, CHILLERS, VALVES, AND INDOOR COILS? | (Y/N) ______ |
LOCATE, REPAIR, AND REPORT ANY LEAKS. ________________________________________________________________