Table 5 — Electrical Data, Alternate Motors

UNIT

V*-PH-Hz

VOLTAGE

 

FAN MOTOR

 

POWER SUPPLY

LIMITS

Hp (kW)

 

FLA

Minimum

MOCP

 

 

 

 

Circuit Amps

 

 

 

 

 

 

 

 

 

 

 

208/230-1-60

187-253

2.4

(1.79)

 

11.0/11.0

13.8/13.8

20

 

 

208/230-3-60

187-253

2.9

(2.16)

 

7.5

9.4

15

40RM

460-3-60

414-506

2.9

(2.16)

 

3.4

4.3

15

007

 

575-3-60

518-632

2.0

(1.49)

 

2.4

3.0

15

 

 

230-3-50

207-253

2.4

(1.79)

 

5.2

6.5

15

 

 

400-3-50

360-440

2.4

(1.79)

 

2.6

3.3

15

 

 

208/230-1-60

187-253

2.4

(1.79)

 

11.0

13.8

15

40RM

 

208/230-3-60

187-253

2.9

(2.16)

 

7.5/7.5

9.4/9.4

15

40RMQ

460-3-60

414-506

2.9

(2.16)

 

3.4

4.3

15

40RMS

 

575-3-60

518-632

3.0

(2.24)

 

3.8

4.8

15

008

 

 

 

 

 

 

 

 

 

 

230-3-50

207-253

2.9

(2.16)

 

7.5

9.4

15

 

 

 

 

 

400-3-50

360-440

2.9

(2.16)

 

3.4

4.3

15

 

 

208/230-1-60

187-253

2.4

(1.79)

 

11.0

13.8

20

 

 

208/230-3-60

187-253

2.9

(2.16)

 

7.5

9.4

15

40RMS

460-3-60

414-506

2.9

(2.16)

 

3.4

4.3

15

010

 

575-3-60

518-632

3.0

(2.24)

 

3.8

4.8

15

 

 

230-3-50

207-253

2.9

(2.16)

 

7.5

9.4

15

 

 

400-3-50

360-440

2.9

(2.16)

 

3.4

4.3

15

40RM

 

208/230-3-60

187-253

3.7

(2.76)

 

10.5/10.5

13.3/13.3

20

 

460-3-60

414-506

3.7

(2.76)

 

4.8

6.0

15

40RMQ

 

 

 

 

 

 

 

 

 

 

575-3-60

518-632

3.0

(2.24)

 

3.8

4.8

15

40RMS

 

 

 

230-3-50

207-253

5.0

(3.73)

 

15.2

19.0

30

012

 

 

 

 

400-3-50

360-440

5.0

(3.73)

 

7.6

9.5

15

 

 

208/230-3-60

187-253

3.7

(2.76)

 

10.2

12.7

20

40RM

 

460-3-60

414-506

3.7

(2.76)

 

4.8

6.0

15

40RMS

 

575-3-60

518-632

5.0

(3.73)

 

5.1

6.4

15

014

 

230-3-50

207-253

5.0

(3.73)

 

15.2

19.0

30

 

 

 

 

 

400-3-50

360-440

5.0

(3.73)

 

7.6

9.5

15

40RM

 

208/230-3-60

187-253

5.0

(3.73)

 

14.6/12.8

18.3/16.0

30/25

 

460-3-60

414-506

5.0

(3.73)

 

6.4

8.0

15

40RMQ

 

 

 

 

 

 

 

 

 

 

575-3-60

518-632

5.0

(3.73)

 

5.1

6.4

15

40RMS

 

 

 

230-3-50

207-253

5.0

(3.73)

 

15.2

19.0

30

016

 

 

 

 

400-3-50

360-440

5.0

(3.73)

 

7.6

9.5

15

40RM

 

208/230-3-60

187-253

7.5

(5.59)

 

21.5/19.4

26.9/24.3

45/40

 

460-3-60

414-506

7.5

(5.59)

 

9.7

12.1

20

40RMQ

 

 

 

 

 

 

 

 

 

 

575-3-60

518-632

7.5

(5.59)

 

7.8

9.8

15

40RMS

 

 

 

230-3-50

207-253

7.5

(5.59)

 

22.8

28.5

50

024

 

 

 

 

400-3-50

360-440

7.5

(5.59)

 

11.4

14.3

25

40RM

 

208/230-3-60

187-253

10.0

(7.46)

 

28.2/26.8

35.3/33.5

60/60

 

460-3-60

414-506

10.0

(7.46)

 

13.4

16.8

30

40RMQ

 

 

 

 

 

 

 

 

 

 

575-3-60

518-632

10.0

(7.46)

 

10.3

12.9

20

40RMS

 

 

 

230-3-50

207-253

10.0

(7.46)

 

32.2

40.3

60

028

 

 

 

 

400-3-50

360-440

10.0

(7.46)

 

16.1

20.1

30

Legend and Notes For Tables 4 and 5

 

LEGEND

FLA

Full Load Amps

MOCP

Maximum Overcurrent Protection

*Motors are designed for satisfactory operation within 10% of nominal volt- ages shown. Voltages should not exceed the limits shown in the Voltage Lim- its column.

Determine maximum deviation from average voltage.

(AB) 397 – 393 = 4 v (BC) 403 – 397 = 6 v (AC) 397 – 396 = 1 v

Maximum deviation is 6 v.

Determine percent voltage imbalance.

NOTES:

1. Minimum circuit amps (MCA) and MOCP values are calculated in accor-

% Voltage Imbalance = 100 x

6

 

dance with NEC (National Electrical Code), Article 440.

2.

Motor FLA values are established in accordance with UL (Underwriters’

 

Laboratories) Standard 1995.

3.

Unbalanced 3-Phase Supply Voltage

 

Never operate a motor where a phase imbalance in supply voltage is

 

greater than 2%. Use the following formula to determine the percentage of

 

voltage imbalance.

max voltage deviation from average voltage

= 100 x

average voltage

EXAMPLE: Supply voltage is 400-3-50.

AB = 393 v

BC = 403 v

AC = 396 v

393 + 403 + 396

Average Voltage =

3

1192

=

3 = 397

397

= 1.5%

This amount of phase imbalance is satisfactory because it is below the maxi- mum allowable 2%.

IMPORTANT: If the supply voltage phase imbalance is more than 2%, contact your local electric utility company immediately.

23