CHECK VOLTAGE IMBALANCE

CHECK VOLTAGE IMBALANCE

 

 

LINE-TO-LINE VOLTS:

AB ________ V

AC ______ V

BC ______ V

(AB + AC + BC)/3 = AVERAGE VOLTAGE = ________ V

 

MAXIMUM DEVIATION FROM AVERAGE VOLTAGE = ________ V

 

VOLTAGE IMBALANCE = 100 X (MAX DEVIATION)/(AVERAGE VOLTAGE) = ___________ %

IF OVER 2% VOLTAGE IMBALANCE, DO NOT ATTEMPT TO START SYSTEM!

CALL LOCAL POWER COMPANY FOR ASSISTANCE.

III. START-UP

CHECK INDOOR FAN MOTOR SPEED AND RECORD.

AFTER AT LEAST 10 MINUTES RUNNING TIME, RECORD THE FOLLOWING MEASUREMENTS:

COMP A1

COMP B1

OIL PRESSURE SUCTION PRESSURE SUCTION LINE TEMP DISCHARGE PRESSURE DISCHARGE LINE TEMP

ENTERING OUTDOOR UNIT AIR TEMP LEAVING OUTDOOR UNIT AIR TEMP INDOOR UNIT ENTERING AIR DB TEMP INDOOR UNIT ENTERING AIR WB TEMP INDOOR UNIT LEAVING AIR DB TEMP INDOOR UNIT LEAVING AIR WB TEMP

OUTDOOR UNIT ENTERING WATER TEMP (40RMS ONLY)

OUTDOOR UNIT LEAVING WATER TEMP (40RMS ONLY)

INDOOR UNIT ENTERING WATER TEMP (40RMS ONLY)

INDOOR UNIT LEAVING WATER TEMP (40RMS ONLY)

COMPRESSOR AMPS (L1/L2/L3)____/____/____ ____/____/____

CHECK THE COMPRESSOR OIL LEVEL SIGHT GLASSES, ARE THE SIGHT GLASSES SHOWING

OIL LEVEL AT 1/ to 1/

3

FULL?

(Y/N) ______

8

 

 

NOTES:

______________________________________________________________________________________________________

______________________________________________________________________________________________________

______________________________________________________________________________________________________

______________________________________________________________________________________________________

______________________________________________________________________________________________________

______________________________________________________________________________________________________

______________________________________________________________________________________________________

______________________________________________________________________________________________________

______________________________________________________________________________________________________

______________________________________________________________________________________________________

______________________________________________________________________________________________________

______________________________________________________________________________________________________

Copyright 2004 Carrier Corporation

Manufacturer reserves the right to discontinue, or change at any time, specifications or designs without notice and without incurring obligations.

Book

1

4

PC 111

Catalog No. 534-00003

Printed in U.S.A.

Form 40RM-23SI

Pg CL-2

12-04

Replaces: 40RM-22SI

Tab

3c

2e

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

- - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - -- - - - - - - - - - - - - - - - - - - - CUT ALONG DOTTED LINECUT ALONG DOTTED LINE

Page 48
Image 48
Carrier 40RMQ008-028, 40RM007-034, 40RMS008-034 specifications Iii. Start-Up, Check Voltage Imbalance