Carrier 40RMQ008-028 Unit Wiring, Fan Contactor Coil Data, Typical Fan Discharge Connections

Models: 40RMS008-034 40RM007-034 40RMQ008-028

1 48
Download 48 pages 9.33 Kb
Page 24
Image 24
Fig. 17 — Unit Wiring

 

LEGEND

EQUIP

Equipment

GND

Ground

HC

Heating Contactor

HTR

Electric Heater

IFC

Indoor-Fan Contactor

IFM

Indoor-Fan Motor

TB

Terminal Block

T’STAT

Thermostat

 

Factory Wiring

 

Field Control Wiring

NOTE: Use copper conductors only.

Fig. 17 — Unit Wiring

Table 6 — Fan Contactor Coil Data

UNIT

VOLTAGE

MAXIMUM

40RM, 40RMQ

HOLDING

(vac)

40RMS

VA

 

007-034

24

10

Connecting Ductwork — Refer to the Carrier System Design Manual for the recommended design and layout of ductwork. Figure 18 shows recommended duct connection to units with 2 fans.

Do not operate unit without ductwork or discharge plenum unless fan speed has been adjusted for external static pres- sure of zero in. wg. Failure to do so may result in motor overload.

DISCHARGE CONNECTIONS — Duct flanges are factory-supplied; they are shipped inside the unit attached to the hairpin end of the coil tube sheet for field installation. Us- ing the existing screws, install the duct flanges on the unit’s fan deck. Each fan discharge requires 2 flanges; each flange must be bent in the middle to conform to the discharge opening. See Fig. 19. After flanges are installed, connect them to the supply duct using a canvas connection to prevent vibration. It is im- portant that this connection be properly fabricated to prevent high air friction losses and air noise.

RETURN CONNECTION — When using return-air duct- work, route return-air duct to the unit’s return air inlet near the filter rack, using a canvas connection to prevent transmission of unit vibration. If the duct blocks off the unit’s access panel, provide a slip joint in the ductwork to permit removal for servicing.

OUTDOOR-AIR INLET CONNECTION — Connect outdoor- air inlet to field-installed accessory economizer. Refer to Economizer Installation Instructions.

Return-Air Filters — Type and size of filters are shown in Tables 1A-1F and are factory-supplied and factory-installed. In all units with 2 fans, a filter replacement tool (hook) is shipped inside the unit for field use when replacing filters. See the Service section for instructions on filter element replacement.

Fig. 18 — Typical Fan Discharge Connections

for Multiple Fan Units

24

Page 24
Image 24
Carrier 40RMQ008-028 Unit Wiring, Fan Contactor Coil Data, Typical Fan Discharge Connections, for Multiple Fan Units