Table 9C — High-Static Drive Data, 60 Hz — English
|
| 40RM |
| 40RM | 40RM | 40RM | 40RM | 40RM | 40RM | |
| 40RM | 40RMQ | 40RMS | 40RMQ | 40RMQ | 40RMQ | 40RMQ | |||
UNIT | 40RMS | 40RMS | ||||||||
007 | 40RMS | 010 | 40RMS | 40RMS | 40RMS | 40RMS | ||||
| 014 | 034 | ||||||||
|
| 008 |
| 012 | 016 | 024 | 028 | |||
|
|
|
|
| ||||||
MOTOR DRIVE |
|
|
|
|
|
|
|
|
| |
Motor Pulley Pitch Diameter (in.) | ||||||||||
Pulley Factory Setting | 2.5 | 2.5 | 2.5 | 2.5 | 3.0 | 3.0 | 3.0 | 3.0 | 3.0 | |
Full Turns Open | ||||||||||
|
|
|
|
|
|
|
|
| ||
FAN DRIVE |
|
|
|
|
|
|
|
|
| |
Pulley Pitch Dia (in.) | 7.0 | 6.0* | 6.0 | 6.0 | 7.4 | 7.9 | 7.4 | 8.6 | 8.6 | |
Pulley Bore (in.) | 1 | 1 | 1 | 1 | 17/16 | 17/16 | 17/16 | 115/16 | 115/16 | |
Belt No. — Section | ||||||||||
Belt Pitch (in.) | 41.3 | 37.3 | 37.3 | 37.3 | 39.8 | 39.8 | 36.8 | 37.8 | 37.8 | |
FAN SPEEDS (rpm) |
|
|
|
|
|
|
|
|
| |
Factory Setting | 961 | 1121 | 1121 | 1121 | 979 | 1060 | 1118 | 1024 | 1024 | |
Range | 838- | 978- | 978- | 978- | 873- | 950- | 1014- | 873- | 873- | |
| 1084 | 1200*† | 1200† | 1200† | 1096 | 1171 | 1200† | 1075 | 1075 | |
Max Allowable Speed (rpm) | 1200 | 1200 | 1200 | 1200 | 1200 | 1200 | 1200 | 1100 | 1100 | |
Change per 1/ Turn of |
|
|
|
|
|
|
|
|
| |
2 | 24.6 | 28.7 | 28.7 | 28.7 | 19.4 | 18.4 | 19.4 | 16.7 | 16.7 | |
Moveable Motor Pulley | ||||||||||
Flange |
|
|
|
|
|
|
|
|
| |
MAX FULL TURNS FROM | 5 | 5 | 5 | 5 | 6 | 6 | 6 | 6 | 6 | |
CLOSED POSITION | ||||||||||
|
|
|
|
|
|
|
|
| ||
SHAFTS CENTER DISTANCE (in.) | 10.44- | 10.44- | 10.44- | 10.44- | 10.44- | 9.16- | 8.16- | 6.67- | 6.67- | |
| 12.32 | 12.32 | 12.32 | 12.32 | 12.32** | 10.99 | 10.02 | 9.43 | 9.43 |
*Values for
†It is possible to adjust drive so that fan speed exceeds maximum allowable. DO NOT exceed 1200 rpm.
Table 9D — Standard Drive Data, 60 Hz — SI
| 40RM | 40RM |
| 40RM | 40RM | 40RM | 40RM | 40RM | 40RM | |
UNIT | 40RMQ | 40RMS | 40RMQ | 40RMQ | 40RMQ | 40RMQ | ||||
40RMS | 40RMS | |||||||||
007 | 40RMS | 010 | 40RMS | 40RMS | 40RMS | 40RMS | ||||
| 014 | 034 | ||||||||
|
| 008 |
| 012 | 016 | 024 | 028 | |||
|
|
|
|
| ||||||
MOTOR DRIVE |
|
|
|
|
|
|
|
|
| |
Motor Pulley Pitch Diameter (mm) | 61.0- | 71.1- | 71.1- | 86.4- | 71.1- | 71.1- | 94.0- | 109.2- | 109.2- | |
| 86.4 | 96.5 | 96.5 | 111.8 | 96.5 | 96.5 | 119.4 | 134.6 | 134.6 | |
Pulley Factory Setting | 2.5 | 2.5 | 2.5 | 2.5 | 2.5 | 2.5 | 3.0 | 3.0 | 3.0 | |
Full Turns Open | ||||||||||
|
|
|
|
|
|
|
|
| ||
FAN DRIVE |
|
|
|
|
|
|
|
|
| |
Pulley Pitch Dia (mm) | 224 | 224 | 224 | 224 | 229 | 229 | 239 | 279 | 279 | |
Pulley Bore (mm) | 25.4 | 25.4 | 25.4 | 25.4 | 36.5 | 36.5 | 36.5 | 49.2 | 49.2 | |
Belt No. — Section | ||||||||||
Belt Pitch (mm) | 1024 | 1049 | 1049 | 1074 | 1074 | 1074 | 1062 | (2) 1087 | (2) 1087 | |
| (2) 1113 | (2) 1113 | ||||||||
|
|
|
|
|
|
|
| |||
FAN SPEEDS (r/s) |
|
|
|
|
|
|
|
|
| |
Factory Setting | 9.5 | 10.8 | 10.8 | 12.7 | 10.5 | 10.5 | 12.9 | 12.5 | 12.5 | |
Range | ||||||||||
Max Allowable Speed (r/s) | 20.0 | 20.0 | 20.0 | 20.0 | 20.0 | 20.0 | 20.0 | 18.3 | 18.3 | |
Change per 1/ Turn of |
|
|
|
|
|
|
|
|
| |
2 | 0.327 | 0.327 | 0.327 | 0.328 | 0.318 | 0.318 | 0.255 | 0.218 | 0.218 | |
Moveable Motor Pulley | ||||||||||
Flange |
|
|
|
|
|
|
|
|
| |
MAX FULL TURNS FROM | 5 | 5 | 5 | 5 | 5 | 5 | 6 | 6 | 6 | |
CLOSED POSITION | ||||||||||
|
|
|
|
|
|
|
|
| ||
SHAFTS CENTER DISTANCE (mm) |
*Four belts shipped with unit. Use correct set of 2 belts sized according to the pulley setting.