![FIRE OR EXPLOSION HAZARD](/images/new-backgrounds/33798/3379825x1.webp)
When installing the gas supply line, observe local codes pertaining to gas pipe installations. Refer to the NFPA 54/ANSI Z223.1 NFGC latest edition (in Canada, CAN/CSA B149.1). In the absence of local building codes, adhere to the following pertinent recommendations:
1.Avoid low spots in long runs of pipe. Grade all pipe
2.Protect all segments of piping system against physical and thermal damage. Support all piping with appro- priate straps, hangers, etc. Use a minimum of one hanger every 8 ft (2.4 m). For pipe sizes larger than
3.Apply joint compound (pipe dope) sparingly and only to male threads of joint when making pipe connec- tions. Use only pipe dope that is resistant to action of liquefied petroleum gases as specified by local and/or national codes. If using PTFE (Teflon) tape, ensure the material is Double Density type and is labeled for use on gas lines. Apply tape per manufacturer’s in- structions.
4.
NOTE: Pressure test the gas supply system after the gas supply piping is connected to the gas valve. The supply piping must be disconnected from the gas valve during the testing of the piping systems when test pressure is in excess of 0.5 psig (3450 Pa). Pressure test the gas supply piping system at pressures equal to or less than 0.5 psig (3450 Pa). The unit heating section must be isolated from the gas piping system by closing the external main manual shutoff valve and slightly opening the
Check for gas leaks at the
!WARNING
FIRE OR EXPLOSION HAZARD
Failure to follow this warning could result in personal injury, death and/or property damage.
SConnect gas pipe to unit using a backup wrench to
avoid damaging gas controls.
SNever purge a gas line into a combustion chamber. S Never test for gas leaks with an open flame. Use a
commercially available soap solution made specifically for the detection of leaks to check all connections.
S Use proper length of pipe to avoid stress on gas control manifold.
BURNER
ORIFICE
A93059 |
| |
Fig. 23 - Orifice Hole | 48TC**16 | |
NOTE: If orifice hole appears damaged or it is suspected | ||
| ||
to have been |
| |
numbered drill bit of correct size. Never |
| |
orifice. A |
| |
essential for proper flame characteristics. See Fig. 23. |
|
Step 11 — Install External Condensate Trap and Line
The unit has one
CONDENSATE PAN (SIDE VIEW) |
| ALTERNATE | ||
STANDARD | DRAIN PLUG | |||
BOTTOM DRAIN | ||||
SIDE DRAIN | ||||
|
|
C08021
Fig. 24 - Condensate Drain Pan (Side View)
When using the standard side drain connection, ensure the red plug in the alternate bottom connection is tight. Do this before setting the unit in place. The red drain pan can be tightened with a
To use the alternate bottom drain connection, remove the red drain plug from the bottom connection (use a
13