Carrier 48TC**16 Outdoor Air Enthalpy Control PNO 33CSENTHSW, LEDs, Differential Enthalpy Control

Models: 48TC**16

1 48
Download 48 pages 56.73 Kb
Page 41
Image 41
Table 9 – LEDs

Table 9 – LEDs

The LEDs on the RTU Open Control Board (see Fig. 65) show the status of certain functions:

If this LED is on...

 

Status is...

 

 

 

Power

 

RTU Open has power

 

 

 

Rx

 

RTU Open is receiving data from the network segment

 

 

RTU Open is transmitting data over the network segment

Tx

 

 

 

The digital output is active

DO#

 

 

 

 

 

The Run and Error LEDs indicate control module and network status

If Run LED shows...

And Error LED shows...

2 flashes per second

Off

 

 

2 flashes per second

2 flashes,

alternating with Run LED

 

2 flashes per second

3 flashes,

then off

 

2 flashes per second

4 flashes,

then pause

 

 

 

2 flashes per second

On

 

 

5 flashes per second

On

 

 

5 flashes per second

Off

 

 

7 flashes per second

7 flashes per second, alternating with

Run LED

 

 

 

14 flashes per second

14 flashes per second,

alternating with Run LED

 

 

 

On

On

 

 

Status is...

Normal

Five minute auto---restart delay after system error

Control module has just been formatted

Two or more devices on this network have the same ARC156 network address

Exec halted after frequent system errors or control programs halted

Exec start---up aborted, Boot is running Firmware transfer in progress, Boot is running

Ten second recovery period after brownout

Brownout

Failure. Try the following solutions:

STurn RTU Open off, then on. S Format RTU Open.

S Download memory to RTU Open. S Replace RTU Open.

48TC**16

NOTE: Refer to Catalog No. 48-50HCTQ-01T for complete configuration of RTU Open, operating sequences and troubleshooting information. Refer to RTU Open Controller Integration Guide (Catalog No. 11-808-428-01) for details on configuration and troubleshooting of connected networks. Have a copy of these manuals available at unit start-up.

Outdoor Air Enthalpy Control (PNO 33CSENTHSW)

The enthalpy control (33CSENTHSW) is available as a field-installed accessory to be used with the EconoMi$er2 damper system. The outdoor air enthalpy sensor is part of the enthalpy control. (The separate field-installed accessory return air enthalpy sensor (33CSENTSEN) is required for differential enthalpy control. See Fig. 80.)

Locate the enthalpy control in the economizer next to the Actuator Motor. Locate two GRA leads in the factory harness and connect the gray lead labeled “ESL” to the terminal labeled “LOW”. See Fig. 80. Connect the enthalpy control power input terminals to economizer actuator power leads RED (connect to 24V) and BLK (connect to GND).

The outdoor enthalpy changeover setpoint is set at the enthalpy controller.

Differential Enthalpy Control —

Differential enthalpy control is provided by sensing and comparing the outside air and return air enthalpy conditions. Install the outdoor air enthalpy control as described above. Add and install a return air enthalpy sensor.

Return Air Enthalpy Sensor —

Mount the return-air enthalpy sensor (33CSENTSEN) in the return-air section of the economizer. The return air sensor is wired to the enthalpy controller (33CSENTHSW). See Fig. 80.

 

 

 

 

4-20

24V

 

 

 

RED

 

 

PL6-1 (24-V)

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Main

GND

 

 

 

BLK

 

 

PL6-4 (COM)

 

 

 

 

+ VDC

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

CTB ECON

 

 

 

 

Out

LOW

 

 

 

GRA

 

 

7

 

 

 

 

 

 

 

 

(P’LINK: to J4-2) or

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

(RTU Open: to J2-6)

 

 

 

 

Outside Air

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Enthalpy Switch

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

+ 24-36

 

 

 

 

Return Air

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

VDC In

 

 

 

 

Enthalpy

 

 

 

 

 

 

4-20 Main

 

 

 

 

Sensor

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Out

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

C11161

 

 

 

 

 

 

 

 

 

 

 

 

 

Fig. 80 - Outside and Return Air Enthalpy Sensor

Wiring

41

Page 41
Image 41