Carrier 48TC**16 Smoke Detector Locations, Supply Air, Return Air without Economizer

Models: 48TC**16

1 48
Download 48 pages 56.73 Kb
Page 43
Image 43
Smoke Detector Locations

Air is introduced to the duct smoke detector sensor’s sensing chamber through a sampling tube that extends into the HVAC duct and is directed back into the ventilation system through a (shorter) exhaust tube. The difference in air pressure between the two tubes pulls the sampled air through the sensing chamber. When a sufficient amount of smoke is detected in the sensing chamber, the sensor signals an alarm state and the controller automatically takes the appropriate action to shut down fans and blowers, change over air handling systems, notify the fire alarm control panel, etc.

The sensor uses a process called differential sensing to prevent gradual environmental changes from triggering false alarms. A rapid change in environmental conditions, such as smoke from a fire, causes the sensor to signal an alarm state but dust and debris accumulated over time does not.

For installations using two sensors, the duct smoke detector does not differentiate which sensor signals an alarm or trouble condition.

Smoke Detector Locations

Supply Air —

The Supply Air smoke detector sensor is located to the left of the unit’s indoor (supply) fan. See Fig. 83. Access is through the left side blower access panel. There is no sampling tube used at this location. The sampling tube inlet extends through the side plate of the fan housing (into a high pressure area). The controller is located on a bracket to the right of the return filter, accessed through the lift-off filter panel.

Smoke Detector Sensor

C08245

Fig. 83 - Typical Supply Air Smoke Detector Sensor

Location

Return Air without Economizer —

 

The sampling tube is located across the return air opening

 

on the unit basepan. See Fig. 86. The holes in the

 

sampling tube face downward, into the return air stream.

 

The sampling tube is connected via tubing to the return air

 

sensor that is mounted on a bracket high on the partition

 

between return filter and controller location. (This sensor

 

is shipped in a flat-mounting location. Installation

 

requires that this sensor be relocated to its operating

 

location and the tubing to the sampling tube be connected.

 

See “Completing Installation of Return Air Smoke

 

Sensor:” for details.)

 

Return Air with Economizer —

 

The sampling tube is inserted through the side plates of

 

 

the economizer housing, placing it across the return air

48TC**16

opening on the unit basepan. See Fig. 84. The holes in the

sensor that is mounted on a bracket high on the partition

sampling tube face downward, into the return air stream.

 

The sampling tube is connected via tubing to the return air

 

between return filter and controller location. (This sensor

 

is shipped in a flat-mounting location. Installation

 

 

requires that this sensor be relocated to its operating

 

location and the tubing to the sampling tube be connected.

 

See the following installation procedure.)

 

Flexible

Exhaust Tube

Return Air

Sampling Tube

C10330

Fig. 84 - Return Air Sampling Tube Location

43

Page 43
Image 43
Carrier 48TC**16 Smoke Detector Locations, Supply Air, Return Air without Economizer, Return Air with Economizer