Carrier 48TC**16 Factory-Option Thru-BaseConnections, Electrical Connections, Thermostat

Models: 48TC**16

1 48
Download 48 pages 56.73 Kb
Page 18
Image 18
Factory-Option Thru-Base Connections

Factory-Option Thru-Base Connections

(Electrical Connections)—

This service connection kit consists of a 1/2-in electrical bulkhead connector and a 11/2-in electrical bulkhead connector, connected to an “L” bracket covering the embossed (raised) section of the unit basepan in the condenser section. See Fig. 36. The 1/2-in bulkhead connector enables the low-voltage control wires to pass through the basepan. The 11/2-in electrical bulkhead connector allows the high-voltage power wires to pass through the basepan.

1/2” ELECTRICAL BULKHEAD CONNECTOR

48TC**16

11/2” ELECTRICAL BULKHEAD CONNECTOR

C10907

Fig. 36 - Thru-the-Base Option, Shipping Position

1.Remove the “L” bracket assembly from the unit.

2.Remove connector plate assembly from the “L” bracket and discard the “L” bracket, but retain the washer head screws and the gasket (located between the “L” bracket and the connector plate assembly).

NOTE: Take care not to damage the gasket, as it is reused in the following step.

3.Place the gasket over the embossed area in the basepan, aligning the holes in the gasket to the holes in the basepan. See Fig. 37.

4.Install the connector plate assembly to the basepan using 8 of the washer head screws.

NOTE: If electrical connections are not going to occur at this time, tape or otherwise cover the fittings so that moisture does not get into the building or conduit in the interim.

CONNECTOR

PLATE

ASSEMBLY

GASKET

C10908

Fig. 37 - Completing Installation of Thru-the-Base

Option

Check tightness of connector lock nuts before connecting electrical conduits.

Field-supplied and field-installed liquid tight conduit connectors and conduit may be attached to the connectors on the basepan. Pull correctly rated high voltage and low voltage through appropriate conduits. Connect the power conduit to the internal disconnect (if unit is so equipped) or to the external disconnect (through unit side panel). A hole must be field cut in the main control box bottom on the left side so the 24-v control connections can be made. Connect the control power conduit to the unit control box at this hole.

Units without Thru-Base Connections —

1.Install power wiring conduit through side panel open- ings. Install conduit between disconnect and control box.

2.Install power lines to terminal connections as shown in Fig. 31.

Field Control Wiring —

The 48TC**16 requires an external temperature control device. This device can be a thermostat (field-supplied) or a PremierLink controller (available as factory-installed option or as field-installed accessory, for use on a Carrier Comfort Network or as a stand alone control) or the RTU Open Controller for Building Management Systems using non-CCN protocols (RTU Open is available as a factory-installed option only).

Thermostat —

Install a Carrier-approved accessory 2 stage Cooling/Heating thermostat according to installation instructions included with the accessory. If using an electronic thermostat, configure it for “non-heat pump” operation. Locate the thermostat accessory on a solid wall in the conditioned space to sense average temperature in accordance with the thermostat installation instructions.

If the thermostat contains a logic circuit requiring 24-v power, use a thermostat cable or equivalent single leads of different colors with minimum of seven leads. If the thermostat does not require a 24-v source (no “C” connection required), use a thermostat cable or equivalent with minimum of six leads. Check the thermostat installation instructions for additional features which might require additional conductors in the cable.

For wire runs up to 50 ft. (15 m), use no. 18 AWG (American Wire Gage) insulated wire (35_C minimum). For 50 to 75 ft. (15 to 23 m), use no. 16 AWG insulated wire (35_C minimum). For over 75 ft. (23 m), use no. 14 AWG insulated wire (35_C minimum). All wire sizes larger than no. 18 AWG cannot be directly connected to the thermostat and will require a junction box and splice at the thermostat.

18

Page 18
Image 18
Carrier 48TC**16 Factory-Option Thru-BaseConnections, Electrical Connections, Thru-the-BaseOption, Shipping Position