Step 13 — Adjust Factory-Installed Options
Smoke Detectors —
Smoke detector(s) will be connected at the Central Terminal Board (CTB), at terminals marked “Smoke Shutdown”. Remove jumper JMP 3 when ready to energize unit.
EconoMi$er IV Occupancy Switch —
Refer to Fig. 87 for general EconoMi$er IV wiring. External occupancy control is managed through a connection on the Central Terminal Board.
If external occupancy control is desired, connect a time clock or remotely controlled switch (closed for Occupied, open for Unoccupied sequence) at terminals marked OCCUPANCY on CTB. Remove or cut jumper JMP 2 to complete the installation.
Step 14 — Install Accessories
Available accessories include:
Roof Curb (must be installed before unit)
Manual outside air damper
Barometric relief Power Exhaust
Differential
Differential enthalpy sensor
Time Guard II compressor
Head pressure control Programmable setback thermostat Electrical/Mechanical thermostat and subbase Thermidistatt device
Humidistat Thermostat / Sensors CO2 sensor
DDC interface (PremierLink) Louvered hail guard
Phase monitor control
Refer to separate installation instructions for information on installing these accessories.
Pre-Start and Start-Up
EconoMi$er IV (with control and integrated barometric relief)
EconoMi$er2 (without control/for external signal and integrated barometric relief)
This completes the mechanical installation of the unit. Refer to the unit’s Service Manual for detailed