Supply Duct Cover
A06320
Fig. 8 - 48XL with Duct Covers On
Provide for Condensate Disposal
NOTE: Ensure that
with local codes, restrictions, and practices.
The units dispose of condensate through a 3/4
fitting that exits on the compressor end of the unit. Condensate water can be drained directly onto the roof in rooftop installations
(where permitted) or onto a gravel apron in ground level
installations. Install a
condensate connection to ensure proper drainage. Make sure that the outlet of the trap is at least 1 in. (25 mm) lower than the
overflowing. Prime the trap with water. When using a gravel apron, make sure it slopes away from the unit.
If the installation requires draining the condensate water away from
the unit, install a
condensate connection to ensure proper drainage. Condensate trap
is available as an accessory or is
overflowing. Connect a drain trough using a minimum of
undersize the tube. Pitch the drain trough downward at a slope of at least 1 in. for every 10 ft. (3 m) of horizontal run. Be sure to check
the drain trough for leaks. Prime the trap at the beginning of the cooling season
Install Flue Hood
CARBON MONOXIDE POISONING HAZARD
Failure to follow this warning could result in personal injury or death.
The venting system is designed to ensure proper venting.
The flue hood assembly must be installed as indicated in this section of the unit installation instructions.
Install the flue hood as follows:
1. This installation must conform with local building codes
and with the National Fuel Gas Code (NFGC), NFPA
54/ANSI Z223.1 (in Canada, CAN/CSA B149.1, and
B149.2) or latest revision. Refer to provincial and local
plumbing or wastewater codes and other @plicable local codes.
2.Remove flue hood from shipping location (inside the return
section of the blower
return duct cover to locate the flue hood. Remove two screws on flue panel. Place flue hood assembly over flue panel. Orient screw holes in flue hood with holes in the flue panel.
3.Secure flue hood to flue panel by inserting a single screw on the top and the bottom of the hood.
1" (25 mm) MIN.
__ | 2" (51 mm) MIN |
A08001
Fig. 9 - Condensate Trap
Install Gas Piping
The gas supply pipe enters the unit through the access hole
provided. The gas connection to the unit is made to the
Install a gas supply line that runs to the heating section. Refer to Table 2 and the current edition of NFOC in the U.S. and the current
NSCNGPIC in Canada. Do not use
recommended that a black iron pipe is used. Check the local utility
for recommendations concerning existing lines. Size gas supply
piping for 0.5 IN. W.C. maximum pressure drop. Never use pipe
smaller than the
For natural gas @plications, the gas pressure at unit gas connection must not be less than 4.0 IN. W.C. or greater than 13 IN. W.C.
while the unit is operating. For propane @plications, refer to
propane conversion kit instructions.
A
connection, must be installed immediately upstream of the gas
supply connection to the gas valve and downstream of manual
equipment shutoff valve.
When installing the gas supply line, observe local codes pertaining
to gas pipe installations. Refer to the NFPA 54/ANSI
(in Canada, CAN/CSA B149.1).
NOTE: In the state of Massachusetts:
1.Gas supply connections MUST be performed by a licensed plumber or gas fitter.
2.When flexible connectors are used, the maximum length shall not exceed 36 in. (915 mm).
3.When lever handle type manual equipment shutoff valves
are used, they shall be
4.The use of copper tubing for gas piping is NOT @proved by the state of Massachusetts.
In the absence of local building codes, adhere to the following pertinent recommendations:
1.Avoid low spots in long runs of pipe. Grade all pipe 1/4 in.
(6.35 mm) for every 15 ft (4.6 m) of length to prevent traps.
Orade all horizontal runs downward to risers. Use risers to connect to heating section and to meter.
2.Protect all segments of piping system against physical and
thermal damage. Support all piping with @propriate straps, hangers, etc. Use a minimum of one hanger every 6 ft. (1.8
m). For pipe sizes larger than 1/2 in., follow
recommendations of national codes.
3.Apply joint compound (pipe dope) sparingly and only to
male threads of joint when making pipe connections. Use
only pipe dope that is resistant to action of liquefied petroleum gases as specified by local and/or national codes. Never use Teflon t@e.
4.Install sediment trap in riser leading to heating section (See
Fig. 10). This drip leg functions as a trap for dirt and condensate.
5.Install an accessible, external, manual main shutoff valve in gas supply pipe within 6 ft (1.8 m) of heating section.
6.Install ground-joint union close to heating section between
unit manual shutoff and external manual main shut off valve.
10