THERMISTOR

CURVE

 

 

9O

I

I

I

 

I

 

 

80- k----4------4-----------4-------....I

 

\

i

i

i

 

i

i

 

7o- -'_-- q------

I----- _------

T------I ....

 

6o-__X__J._ _ _ .I___ __

_ _ J__ _ _I....

 

50....

\i

i

i

 

i

i

 

'_------

1-----

_------

1-------I ....

 

40- -

/_.__

l______/___l

 

....

 

30....

I\

I

I

 

I

I

 

_----_'-Z_----------I-------....I

 

20....

_ ______/'_._/__

____/ ____--I....

 

 

I

I

_

 

I

I

 

lo....

H---

t---..................._--_--

I

I,,-,

 

o

I

I

I

 

 

0

20

40

60

 

80

100

120

 

TEMPERATURE

(DEG. F)

 

 

A91431

Fig. 25 - Resistance Values Versus Temperature

THERMISTOR SENSOR COMPARISON

The control continuously monitors and compares the outdoor air

temperature sensor and outdoor coil temperature sensor to ensure

proper operating conditions. The comparison is:

In cooling mode, if the outdoor air sensor indicates -> 10 °F

(-12°C) warmer than the coil sensor (or) the outdoor air sensor indicates -> 20 °F cooler than the coil sensor, the sensors are out of range.

>o ,_o

In heating if the outdoor air sensor indicates _ 35 F (_ C) warmer than the coil sensor (or) the outdoor air sensor indicates

-> 10°F (-12°C) cooler than the coil sensor, the sensors are out of range.

If the sensors are out of range, the control will flash the appropriate fault code as shown in Table 5.

The thermistor comparison is not performed during low ambient cooling operation.

FAILED THERMISTOR DEFAULT OPERATION

Factory defaults have been provided in the event of failure of

outdoor air thermistor and/or coil thermistor.

If the OAT sensor should fail, low ambient cooling will not be

allowed and the one-minute outdoor fan off delay will not occur.

Defrost will be initiated based on coil temperature and time.

If the OCT sensor should fail, low ambient cooling will not be

allowed. Defrost will occur at each time interval during heating operation, but will terminate after 5 minutes.

If there is a thermistor out of range error, defrost will occur at each

time interval during heating operation, but will terminate after 5 minutes.

Refer to the Troubleshooting Chart (Table 10) for additional

troubleshooting information.

"tub

\

 

J

o

 

_

tight on the

liquid

 

 

g

F

 

 

 

A06311

Fig. 26 - Outdoor

Coil Thermistor

(OCT)

Attachment

FINAL CHECKS

IMPORTANT:

Before leaving job, be sure to do the following:

1.Ensure that all wiring is routed away from tubing and sheet

metal edges to prevent rub-through or wire pinching.

2.Ensure that all wiring and tubing is secure in unit before

adding panels and covers. Securely fasten all panels and covers.

3.Tighten service valve stem caps to l/2-turn past finger tight.

4.Leave Users Manual with owner. Explain system operation

and periodic maintenance requirements outlined in manual.

5.Fill out Start-Up Checklist located at the back of this manual and place in customer file.

CARE AND MAINTENANCE

For continuing high performance and to minimize possible

equipment failure, periodic maintenance must be performed on this equipment.

Frequency of maintenance may vary depending upon geographic

areas, such as coastal applications. See Users Manual for information.

32

Page 32
Image 32
Carrier 48XL installation instructions Thermistor Sensor Comparison, Failed Thermistor Default Operation, Oct