-Defrost operation
-Low ambient cooling
-Crankcase heater operation
-Compressor external protection
-Pressure switch monitoring (refrigerant)
-Time delays
FURNACE BOARD
The furnace board controls the following functions:
-Indoor blower operation
-Gas valve
-Inducer motor
-Remote sparker module
-Pressure switch monitoring (gas)
SYSTEMS COMMUNICATION FAILURE
If communication with the Infinity Control is lost with the UI, the
controls will flash the appropriate fault codes. Check the wiring to the UI, indoor and outdoor units.
MODEL PLUG
The HP/AC control board must have a valid model plug to operate. If a valid model plug is not detected, it will not operate and the
control will flash the appropriate fault code, shown in Table 5.
PRESSURE SWITCH PROTECTION-REFRIGERANT
The unit is equipped with high- and
control senses the opening of a high- or
1.
compressor solenoid contactor (HPS2).
2.Keep the outdoor fan operating for 15 minutes.
3.Display the appropriate fault codes.
4.After a 15 minute delay, if there is still a call for cooling and
the LPS or HPS is reset, the compressor contactor is energized.
5.If LPS or HPS has not closed after a 15 minute delay, the outdoor fan is turned off. If the open switch closes anytime
after the
6.If LPS or HPS trips 3 consecutive cycles, the unit operation is locked out for 4 hours.
7.In the event of a
lockout, check the refrigerant charge, outdoor fan operation and outdoor coil for airflow restrictions.
8.In the event of a
CONTROL FAULT
If the HP/AC control board has failed, the control will flash the
appropriate fault code (See TaMe 5). The control board should be replaced.
BROWN OUT PROTECTION
If the line voltage is less than 187v for at least 4 seconds, the
appropriate compressor contactor and fan relay are
Compressor and fan operation are not allowed until voltage is a
minimum of 190v. The control will flash the appropriate fault code (See Table 5).
230V LINE (POWER DISCONNECT) DETECTION
If there is no 230v at the compressor contactor when the unit is
powered and cooling demand exists, the appropriate error code is
displayed. Verify that the disconnect is closed and 230v wiring is connected to the unit.
COMPRESSOR VOLTAGE SENSING
The control board input terminals VS and L2 (See Fig. 18) are
used to detect compressor voltage status, and alert the user of
potential problems. The control continuously monitors the high
voltage on the run capacitor of the compressor motor. Voltage
should be present any time the compressor contactor is energized,
and voltage should not be present when the contactor is
CONTACTOR SHORTED DETECTION
If there is compressor voltage sensed when there is no demand for
compressor operation, the contactor may be stuck closed or there is
a wiring error. The control will flash the appropriate fault code.
COMPRESSOR THERMAL CUTOUT
If the control senses the compressor voltage after
then | absent | for 10 | consecutive |
| seconds | while | cooling | demand | ||||||||
exists, |
| the | thermal | protector | is | open. | The | control | the | |||||||
compressor | contactor | for | 15 minutes, | but | continues | to operate | the | |||||||||
outdoor | fan. | The | control | Status | LED will flash the appropriate | |||||||||||
code | shown | in | Table | 5. | After | 15 | minutes, |
| with | a call for | low | or | ||||
high | stage | cooling, |
| the | compressor |
| contactor | is energized. | If | the |
thermal protector has not
the call | for | cooling | continues, | the | control | will | energize | the | |||
compressor | contactor | every | 15 | minutes. | If | the | thermal | protector | |||
closes (at | the | next 15 | minute | interval), | check | the | unit | will resume | |||
operation. |
|
|
|
|
|
|
|
|
|
|
|
If the thermal | cutout | trips for | three consecutive | cycles, | then | unit |
operation is locked out for 4 hours and the appropriate fault code is
displayed.
NO 230V AT COMPRESSOR
If the compressor voltage is not sensed when the compressor
should be starting, the contactor may be stuck open or there is a
wiring error. The control will flash the appropriate fault code. Check the contactor and control box wiring.
TROUBLESHOOTING UNIT FOR PROPER SWITCHING
BETWEEN LOW & HIGH STAGES
Check the suction pressures at the service valves. Suction pressure
should | be | reduced | by | when | switching | from | low | to | high | ||||||
capacity. |
|
|
|
|
|
|
|
|
|
|
|
|
|
| |
NOTE: | The | liquid | pressures |
| are | very | similar | between | low | and | |||||
high | stage | operation, |
| so | liquid | pressure | should | not | be used | for | |||||
troubleshooting. |
|
|
|
|
|
|
|
|
|
|
|
| |||
Compressor | current should increase | ||||||||||||||
low to | high | stage. | The | compressor | solenoid, | when | energized | in | |||||||
high stage, should measure 24vac. |
|
|
|
|
|
| |||||||||
COMPRESSOR | INTERNAL | RELIEF |
|
|
|
|
| ||||||||
The | compressor | is | protected | by | an | internal pressure relief (IPR) | |||||||||
which |
| relieves | discharge |
| gas | into | compressor | shell | when |
differential between suction and discharge pressures exceeds 550 -
625 psi. The compressor is also protected by an internal overload attached to motor windings.
TEMPERATURE THERMISTORS
Thermistors are electronic devices which sense temperature. As the
temperature increases, the resistance decreases. Thermistors are
used to sense outdoor ambient (OAT) and coil temperature (OCT).
Refer to Fig. 25 for resistance values versus temperature. See Fig. 26 for OCT location.
If the outdoor ambient or coil thermistor should fail, the HP/AC
control | will | flash the | appropriate | fault code (See Table 5). |
| |||||
IMPORTANT: |
| Coil | thermistor | is factory mounted. | Check | to | ||||
insure | thermistor | is | mounted | properly. | Outdoor | air | thermistor | |||
(OAT) | is field | mounted | and connected. | Verify that | the | OAT | has | |||
been | properly | installed. |
|
|
|
|
|
|
31